Maximum number of connections when using AS300 to connect to other devices through Ethernet/IP:
AS300 can act as a Scanner and an Adapter simultaneously. It can connected up to 16 devices (for example 8
Scanners and 8 Adapters).
When AS300 acts as a Scanner, it can connect to up to 16 devices. Each device can establish up to 32
connections for data mapping. Data mapping types can be I/O connection and Consumed TAG. You can use
explicit message for data mapping at the same time, up to 16 explicit message connections can be created.
When AS300 acts as an Adapter, it can connect to up to 16 devices. Each device can establish up to 8
connections for data mapping. Data mapping types can be I/O connection and Produced TAG. You can use explicit
message for data mapping at the same time, up to 8 explicit message connections can be created.
9.3.3

PROFINET Specification

Communication Protocol
EtherNet/IP Interface
Fieldbus
Network Cable Length
Error Indicator
Max. Connection Number
Register to Read and Write
_9
Minimum Time for Data Exchange to Operate
Maximum Data Length/Per Transmission
PROFINET Configuration
9 - 1 2
Item
Number
Max. Data Length
Requested Packet
Interval (RPI)
Item
AS300 Series
AS200 Series
500 bytes (IO Connection)
400 bytes (Explicit Message)
5 ms – 1000 ms
Specification
PROFINET RT
100 Mbit with 2 x RJ45
PROFINET Devices
100 meter
System Fail (SF): Red; Bus Fail (BF): Red
17
AS300 series data registers are supported to read and write
10 ms
Input: 250 words
Output: 250 words
Download PROFINET Configurations from PN Controller
Remarks