Delta AS Series Operation Manual page 257

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

Category
Error Code
H'11010126
H'11010129
H'11010132
H'12010100
H'12010106
H'12010110
Data
H'12010111
Exchange
Setup Error
H'12010113
H'12010119
H'12010127
H'12010128
C h a p t e r 9 E t h e r n e t S p e c i f i c a t i o n a n d O p e r a t i o n
Description
EDS file are mismatched.
The configuration size
parameters in the EDS file
are mismatched.
The configuration path
parameters in the EDS file
are mismatched.
The EDS file does not
support Null forward open.
I/O connections duplicated
Ownership conflict
Target for connection not
configured
Adapter RPI not supported
Out of connections
Non-Listen only not opened
Invalid originator to target
Size
Invalid target to originator
How to fix them
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
1. Check if the product information and the EDS
file match.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
1. Check if the product information and the EDS
file match.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
1. Check if the product information and the EDS
file match.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
1. Check if the system has created the I/O
connections.
2. Change the connection type to Listen Only.
1. Check the scanner owner.
2. Reconfigure the invalid scanner.
3. Change the connection to multicast.
1. Check the I/O connection status.
2. Activate the I/O connections again.
Check the RPI for the adapter.
1. Check if the number of connections exceeds
the limit.
2. Reduce the number of the product connections.
1. Check if the system has created the I/O
connections.
2. Check the scanner I/O connection status.
Check the module number and the product setup
file to see if they match.
Check the output size in the connection
9_
9 - 4 9