Delta AS Series Operation Manual page 100

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

Number
Name
3
Address switch
Function switch
4
DeviceNet communication
5
port
Mode switch
6
(RTU/DNET;
Master/Slave)
7
Left-side extension port
8
Label
9
Right-side extension port
Input for supplying power
10
to remote modules
2 - 6 6
C h a p t e r 2 S p e c i f i c a t i o n s a n d S y s t e m C o n f i g u r a t i o
Description
RTU mode:
 NS LED
OFF: no power or duplicate ID check has not been
completed.
Green light blinking every 0.5 seconds: the connection
to the DeviceNet network failed.
Green light ON: online; the connection to the DeviceNet
network is normal.
Red light blinking every 0.5 seconds: I/O connection
timeout between AS01DNET (RTU) and DeviceNet master
Red light ON: Network trouble, duplicate node ID, no
network power or Bus-OFF.
 MS LED
OFF: no power
Green light blinking every 0.5 seconds:
- AS01DNET (RTU) is waiting for the I/O data from
DeviceNet master.
- No I/O data transmission between AS01DNET(RTU) and
DeviceNet master
- The PLC connected to DeviceNet master is in STOP state.
Green light ON: normal transmission of I/O data between
AS01DNET (RTU) and DeviceNet master
Red light blinking every 0.5 seconds: no network power
supply; configuration error; module alarms.
Red light ON: hardware error
Setting up the address
Setting up the funcitons, including the work mode and baud rate
of
DeviceNet network
Connects the modules via DeviceNet communication.
Use AS01DNET-A connector for wiring.
Master/Slave mode: the port does not need an external
24VDC power supply connected
RTU mode: the power input port of the network module is
required to connect an external 24VDC power supply only.
You can connect
Connects the modules
Nameplate
Connects the modules
Power supply for the remote module
n
2_