A S S e r i e s O p e r a t i o n M a n u a l
Not using the FCOMP card or not in the
right mode for the ASDA-A2 while using
2001
the CANopen communication
instruction.
The device used in the program
2003
exceeds the device range.
The operand n or the other constant
200B
operands K/H exceed the range.
_12
200C
The operands overlap.
The binary to binary-coded decimal
200D
conversion is incorrect.
200E
The string does not end with 00.
2012
Incorrect division operation
The value exceeds the range of values
2013
that can be represented by the floating-
point numbers.
The task designated by the TKON or
2014
YKOFF instruction is incorrect or
exceeds the range.
The instruction BREAK is written
2017
outside of the FOR-NEXT loop.
No such position planning table number
2027
or the format is incorrect.
High speed output instruction is being
2028
executed. Only one instruction can be
executed at a time.
During the execution of CSFO
2030
instruction, the output frequency
exceeds the upper limit.
During the execution of CSFO
instruciotn, when the output frequency
2031
is set to 0, but even after 2 seconds, the
output is still not complete.
6004
The IP address filter is set incorrectly.
600D
RJ45 port is not connected.
There are devices using the same IP
6012
address.
6100
The email connection is busy.
The trigger attachment mode in the
6103
email is set incorrectly.
1 2 - 1 2
1. Use the FCOMP card in the function card slot to
check if the operation mode is correct.
2. Check the syntax error step in the program.
Modify and compile the program and then
download the program again.
Check the syntax error step in the program. Modify
and compile the program and then download the
program again.
1. Check the syntax error step in the program.
Modify and compile the program and then
download the program again.
2. Check the settings of the position planning table.
Refer to SR28 for the record of the axis number
and rearrange the output control procedures.
Modify the ratio of input / output frequency or lower
the inut frequency value.
Set the Ethernet parameter for the CPU module in
HWCONFIG again.
Check the connection.
1. Check if there are devices using the same IP
address.
2. Check if there is more than 1 DHCP or BOOTP
server on the network.
Retry the email connection later. This error does
not cause the PLC to stop running. Solve the
problem by means of the related flag in the
program.
Set up the trigger attachment mode in HWCONFIG
> CPU Module > Device Setting > Options >
Ethernet Port Advanced > Email > Trigger Setting
> Trigger Attachment Mode.
SM0
V
SM0
V
SM0
V
SM0
V
SM0
V
SM0
V
SM0
V
SM0
V
SM0
V
SM0
V
SM0
V
V
-
V
-
V
-
SM1108
X
SM1100
X
SM1101
V
SM1113
X
SM1113
X

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents