A S S e r i e s O p e r a t i o n M a n u a l
*You can also enter the IP address to be connected to other TAGs so that creating a General Device is not
necessary.
d)
Selecting the Consumed TAG
Select the created Consumed TAG from the CPU register address /TAG column.
e)
Enter the name for the to-be-connected Produced TAG.
After you select the TAG, the software shows the same TAG name in the register address / parameters /
address for the Adapter. You can modify the TAG name to have the same name as the Produced TAG
name.
Set the properties
Click the ... button to set the properties.
a)
b)
In the Property Setting dialog box, enter the data mapping parameters.
Set the Requested Packet Interval (RPI) to refresh the data between the Scanner and Adapter
periodically; for example, every 20ms.
_9
9 - 3 8