Chapter 1 Introduction; Specification - Delta DVP02TK-S Manual

Temperature control module
Hide thumbs Also See for DVP02TK-S:
Table of Contents

Advertisement

1.1 Specification

Supply voltage
24VDC
Max. rated power
2.4W, supplied by external power source in compliance with UL61010-2-201 \ IEC61131-2
consumption
Connector Type
European standard removable terminal block (Pin pitch: 3.5mm)
Operation: 0°C ~ 55°C (temperature), 5 ~ 95% (humidity), Pollution degree: 2
Operation/storage
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity), Attitude: up to 2000m;
temperature
For use in dry location only
Vibration/Shock
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc) / IEC 61131-2 & IEC 68-2-27 (TEST
resistance
Ea)
Connection to
The modules are numbered from 0 to 7 automatically by their distance from DVP-PLC. Max. 8
DVP-PLC
modules are allowed to connect to DVP-PLC and will not occupy any digital I/O points.
2 points of universals analog inputs (CH1, CH2), 2 analog outputs (OUT1, OUT2) or 4 digital
I/O points
outputs (OUT1~OUT4)
Thermal resistance: Pt100, JPt100, Pt1000, Ni100, Ni1000, Cu50, Cu100, GNi1000
CH1,
Thermocouple : J, K, R, S, T, E, N, B, U, L, TXK (L), C, PL II
Input
CH2
Voltage input: 0~+50mV, 0~+5V, 0~+10V
Current input: 0mA~+20mA, 4~+20 mA
Hardware Resolution
16 bits
Distance
100 meters
Input disconnection
Supported by exceeded temperature input range
detection
OUT1~
Analog
Analog output, 12-bit: 0~+10V, 0/4~+20mA
OUT2
OUT1~
4 channels digital output, 250VAC, 60Hz/24VDC, 2A, Relay
Digital
OUT4
4 channels digital output, Voltage pulse output, 24VDC, 300mA
A/D Function Specification
Analog / Digital
Maximum rated input
Overall accuracy
(normal temperature)
Overall accuracy
(full temperature range)
Hardware resolution
DVP02TK-S/DVP02TU-S
General Analog Input
Analog / Digital Output
Voltage Input
0V~10V
0.5%
1%
16 bits
C h ap t e r 1 I nt r odu ct io n
0V~5V
1_
1 - 3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dvp02tu-s

Table of Contents