Error Handling - Siemens SIMATIC PCS 7 Function Manual

Process control system, advanced process functions apf
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

In/out parameters
The following table shows the in/out parameters of the "FB_XXXA" block:
Parameter
APF_AS
APF function block version in AS
APF_OS
APF function block version in OS
GEN_AS
Generation information in AS
GEN_OS
Generation information in OS
"x": WinCC tag available; "-": WinCC tag not available
8.1.5

Error handling

Block error
Errors occurring in the block are signaled via an integrated "ALARM_8P" block and displayed
at the digital outputs of the block. They can be analyzed by the requesting block on the basis
of the output structure. The error bits are available at the block as output signals. In this case,
the "WR_OK" output is not set.
The following error messages can be generated:
MON_ERR
Advanced Process Functions (APF)
Function Manual, 07/2016, A5E38719883-AA
Description
Output structure
QPARAMF
QERR
QMONERR
QRCIDERR
QWM_ERR
QWM_AERR
QWM_CERR
QWM_PERR
QERR_VER
WORD
WORD
DWORD
DWORD
Output
Parameter assignment error;
ID, ARCH_NO or TIME_MON <= 0, or ARCH_NA=''
Data error
REQ_ID in request and receive structure not the same
Runtime error;
Monitoring timeout
Specification error;
REC_ID <= 0
Error from FB_UA_W: Data error,
job data in WinCC communication interface do not corre‐
spond to original job data
Error from FB_UA_W: Archive error;
job data in the WinCC communication interface reset by the
OS, or script error occurred in OS
Error from FB_UA_W: Communication error;
Error message from "BSEND" coupling blocks
Error from FB_UA_W: Parameter assignment error;
incorrect ID_1, R_ID_1 or ID_2, R_ID_2 or duplicate REQ_ID
Error in the version information
Archive management
8.1 FB_XXXA (FB_XXXAI, FB_XXXAR)
Type
Default
0
0
0
0
Meaning
WinCC tag
x
x
x
x
219

Advertisement

Table of Contents
loading

Table of Contents