Order management
7.1 FB_JOB
The operator control enable signals are available at the corresponding block outputs.
"Start"
"Hold"
"Resume"
"End"
"Abort"
"Automatic"
"Manual"
"Internal"
"External"
"Cyclic mode"
"One time mode"
"New"
"Delete"
178
Function
OP_EN
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Output
EN_START
● "Manual" mode
● Job available
● Job released
● Job processing not started
EN_HOLD
● "Manual" mode
● Job not paused
● Job processing ON
● "Hold" job is not active
EN_RESUM
● "Manual" mode
● Job paused
● Job released
● Job not aborted
● Job processing ON
● "Resume" job is not active
"JOB_ON"
EN_END
● "Manual" mode
● Job not aborted
● Job processing ON
● "End" job is not active
● "JOB_ON"
EN_ABORT
● "Manual" mode
● Job available
● "Abort" job is not active
EN_AUT
"Manual" mode
EN_MAN
"Automatic" mode
EN_INT
"External" mode
EN_EXT
"Internal" mode
"Create job" not active
EN_CYCL
"One time" mode
EN_ONETI
"Cyclic" mode
EN_NEW
● "Internal" mode
● Job list not full
● Data request via "FB_XXXPA" is not active
● No pending data request errors
EN_DEL
● "Internal" mode
● Job selected in list
Additional conditions
Advanced Process Functions (APF)
Function Manual, 07/2016, A5E38719883-AA

Advertisement

Table of Contents
loading

Table of Contents