Messaging - Siemens SIMATIC PCS 7 Function Manual

Process control system, advanced process functions apf
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Order management
7.1 FB_JOB
7.1.6

Messaging

The "FB_JOB" block uses six "ALARM_8P" blocks to generate messages. Following CPU
startup, messages are suppressed (QMSG_SUP = 1) until the "RUNUPCYC" cycles have
elapsed.
ALARM_8P_1
ALARM_8P_1 is used to output fault messages and free external messages:
Message
Message class
SIG_1
AS process control
Message - fault
SIG_2
SIG_3
SIG_4
SIG_5
SIG_6
AS process control
Message - error
SIG_7
Process message – with
acknowledgment
SIG_8
Operating message – with‐
out acknowledgment
The following keywords are used:
● $$BlockComment$$: instance-specific block comment.
● $$HID$$ source
● $$AREA$$: OS_AREA
● @1%s@: Batch ID
The following associated values are used:
SD_1
SD_2
SD_3
SD_4
SD_5
SD_6
SD_7
SD_8
SD_9
SD_10
200
Input
"CSF"
Input
"FB_ERROR"
None
None
Input
"EXT_MSG5"
Input
"EXT_MSG6"
Input
"EXT_MSG7"
Input
"EXT_MSG8"
Associated value
Event
$$BlockComment$$ control system fault
$$BlockComment$$ external fault
$$BlockComment$$ A8P_1 SIG3
$$BlockComment$$ A8P_1 SIG4
$$BlockComment$$ external message input
EXT_MSG5
$$BlockComment$$ external message input
EXT_MSG6
$$BlockComment$$ external message input
EXT_MSG7
$$BlockComment$$ external message input
EXT_MSG8
Format
@1%s@
-
-
-
-
@6
@7
@8
@9
@10
Message text
Value
BA_NA
AS input "AUX_PR06"
AS input "AUX_PR07"
AS input "AUX_PR08"
AS input "AUX_PR09"
AS input "AUX_PR010"
Advanced Process Functions (APF)