Siemens SIMATIC PCS 7 Function Manual page 91

Process control system, advanced process functions apf
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

The following error messages can be generated:
Request structure
MON_ERR
Booking errors
In contrast to normal troubleshooting, a special error output and the setting of the "NEW_DATA"
output indicate those errors occurring during operation which are not related to communication
between FB_ST_AC / FB_UA_RM / OS script:
QMLOTMAX
QREL_ERR
QMLOTERR
QCONTERR
QFORMERR
QOV_DINT
QMAT_ERR
QUOM_ERR
QMLIDERR
QAVALERR
QDST_ERR
Advanced Process Functions (APF)
Function Manual, 07/2016, A5E38719883-AA
Output
QPARAMF
QERR
QMONERR
QRM_ERR
QRM_AERR
QRM_CERR
QRM_PERR
Output
All storage locations full, booking not possible
Release error: Violation of a criterion for accounting mode valid at storage location
Material lot not available, booking not possible
More booked/cleared than the number defined at the storage location
(CONT_MAX or CONT_MIN column)
When the target total quantity > CONT_MAX, the target total quantity is written to
the user archive (STOR_CONT column).
When the target total quantity < CONT_MIN, CONT_MIN is written to the user
archive.
Formats of the booking and the storage location do not match (e.g. Booking of
REAL values in an INTEGER storage location)
DINT overflow: Total booked to storage location exceeds maximum DINT value
limit
Incorrect material in the storage location, material lot cannot be booked
Unit cannot be converted to unit in storage location
Specified material lot = 0, booking job is not started
Specified quantity = 0, booking job is not started
Specified destination storage location ID = 0 (only relevant in "Material lot rebook"
mode)
Parameter assignment error;
ID or TIME_MON <= 0
Data error
REQ_ID in request and receive structure not the same
Runtime error;
Monitoring timeout
Error from FB_UA_RM: Data error,
job data in WinCC communication interface do not corre‐
spond to original job data
Error from FB_UA_RM: Archive error;
job data in the WinCC communication interface reset by the
OS, or script error in the OS
Error from FB_UA_RM: Communication error;
Error message from "BSEND" coupling blocks
Error from FB_UA_RM: Parameter assignment error;
incorrect ID_1, R_ID_1 or ID_2, R_ID_2 or duplicate REQ_ID
Meaning
Storage location management
5.3 FB_ST_AC
Meaning
91