Creating a job
In "External" mode, a job can be created using the following inputs. For a job to be successfully
applied, it must have a name, an ID, a valid parameter set number and possibly also a setpoint
(depending on whether or not it is a reference quantity).
EXT_IT
0
1
Advanced Process Functions (APF)
Function Manual, 07/2016, A5E38719883-AA
Input
EXT_NEW
"EXT_NEW" = 1 initiates the creation of a job. After the job data has
been specified at the inputs, the order data record is entered in the job
list with "EXT_TAOV" = 1. "EXT_NEW" = 0 cancels the creation of a job.
EXT_RCTL
The name is specified at the "EXT_RCTL" (record title) input. This input
is only relevant if "automatic name specification" is not activated at the
AS "MODE" input.
EXT_RCID
The ID is specified at the "EXT_RCID" (record id) input. This input is
only relevant if "automatic ID specification" is not activated at the AS
"MODE" input.
EXT_RCPN
The parameter set number is specified at the "EXT_RCPN" (record pa‐
rameter set number) input. The parameter set number must be available
in the corresponding user archive.
EXT_RCSP
The "setpoint" is specified at the "EXT_RCSP" (record setpoint) input.
This input is only relevant if the preselected parameter set number is a
reference quantity.
EXT_RCDS
A job description can be specified at the "EXT_RCDS" (record descrip‐
tion) input.
IT_NEW
"IT_NEW" = 1 initiates the creation of a job. After the job data has been
specified at the inputs, the order data record is entered in the job list
with "IT_TAOV" = 1. "IT_NEW" = 0 cancels the creation of a job.
IT_RCTL
The name is specified at the "IT_RCTL" (record title) input. This input
is only relevant if "automatic name specification" is not activated at the
AS "MODE" input.
IT_RCID
The ID is specified at the "IT_RCID" (record id) input. This input is only
relevant if "automatic ID specification" is not activated at the AS "MODE"
input.
IT_RCPN
The parameter set number is specified at the "IT_RCPN" (record pa‐
rameter set number) input. The parameter set number must be available
in the corresponding user archive.
IT_RCSP
The "setpoint" is specified at the "IT_RCSP" (record setpoint) input. This
input is only relevant if the preselected parameter set number is a ref‐
erence quantity.
IT_RCDS
A job description can be specified at the "IT_RCDS" (record description)
input.
Order management
Description
7.1 FB_JOB