Parameter
TIME_MON
REC_ST
MSG_EVID
Output parameters
The following table shows the output parameters of the "FB_XXXMA" block:
Parameter
QRUN_UP
QNOT_OK
QGR_ERR
QPARAMF
QRELEASED
QERR
QERR_VER
QMON_ERR
QLEN_ERR
QRM_ERR
QRM_AERR
QRM_CERR
QRM_PERR
QREQ_ACT
NEW_DATA
REQ_ST
QID
QARCH_NA
QARCH_NO
QREC_ID
QNO_REC
QCOLUMN
Advanced Process Functions (APF)
Function Manual, 07/2016, A5E38719883-AA
Description
Monitoring time for read job
Feedback structure from FB_UA_RM
ALARM_8P option: EV_ID
Description
Status display, startup active = 1
Block flag "OK" not set,
Error = 1
Group error/fault
1 = Parameter assignment error, ID=0 or
REC_ID=0 or ARCH_NA=' ' or TIME_MON=0
1= Function block released for processing
1 = Read error,
Header: requested data and read data do not
match
1 = Version check error
1 = Read job monitoring timeout
1 = Length of the read data does not corre‐
spond to length of block outputs
FB_UA_RM: 1 = Read error, requested data
and read data do not match
FB_UA_RM: 1 = Archive error, invalid data in
receive buffer
FB_UA_RM: 1 = Communication error, error
message from "BRCV" coupling blocks
FB_UA_RM: 1 = Parameter assignment er‐
ror, duplicate REQ_ID or incorrect ID_1,
R_ID_1 or ID_2, R_ID_2
Read job active
Data have been read
Request structure to FB_UA_RM
Read data: ID
Read data: Archive name
Read data: Archive number
Read data: Data record number in user ar‐
chive
Read data:
Number of rows to be read
Read data:
Column number at which reading commen‐
ces
Material management
3.1 FB_XXXMA
Type
REAL
30.0
UDT_UA_R_ST
DWORD
0
Type
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
UDT_UA_R_REQ_
ST
INT
0
STRING[16]
''
DINT
0
DINT
0
DINT
0
DINT
0
Default
Default
35