Siemens SIMATIC PCS 7 Function Manual page 98

Process control system, advanced process functions apf
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Storage location management
5.4 FB_STLOC
Parameter
LVALUE5B
Interconnectable input:
Value 5 (date part 2)
LVALUE6
Interconnectable input: Value 6 (date part 1)
LVALUE6B
Interconnectable input: Value 6 (date part 2)
OP_EN
Enabled operations
HIDE_BUT
Hide buttons
MODE
Mode
MSG_EVID
ALARM_8P: EV_ID
"MODE" parameter
You can define the mode of the block using the input word "MODE":
Bit
0
EDGE_START_NEC
1
QSEL_ERR_MSG
2
QRUN_ERR_MSG
"OP_EN" parameter
You can enable button operation in the faceplate with the input word "OP_EN". This enable is
only effective if the mode allows button operation.
Bit
0
AUT
1
MAN
2
3
POSITION
4
SEARCH
98
Description
Name
0 = Positive edge at the "L_START" input required.
1 = No positive edge at the "L_START" input required.
0 = OS QSEL_ERR message deactivated
1 = OS QSEL_ERR message is active
0 = OS QRUN_ERR message deactivated
1 = OS QRUN_ERR message is active
Name
0 = "Auto" operation disabled
1 = "Auto" key, external enable for operation
0 = "Manual" operation disabled
1 = "Manual" key, external enable for operation
not used
0 = "Storage location selection" operation disabled
1 = "Storage location selection", external enable for operation
0 = "Search" operation disabled
1 = "Search" key, external enable for operation
Type
Default
DWORD
16#0
DWORD
16#90010100
DWORD
16#0
WORD
16#FFFF
WORD
0
WORD
0
DWORD
0
Meaning
Meaning
Advanced Process Functions (APF)
Function Manual, 07/2016, A5E38719883-AA
OS
tag
-
-
-
-
-
-
-

Advertisement

Table of Contents