I/Os - Siemens SIMATIC PCS 7 Function Manual

Process control system, advanced process functions apf
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Archive management
8.1 FB_XXXA (FB_XXXAI, FB_XXXAR)
An error message is output after the last repetition.
Exception: The job is not repeated after inserting (WREQ_INS).
8.1.4

I/Os

Input parameters
The following table shows the input parameters of the "FB_XXXA" block:
Parameter
SAMPLE_T
RUNUPCYC
ID
ARCH_NA
ARCH_NO
REC_ID
BA_NA
BA_ID
COUNT
TIME_MON
W_REC_ST
WREC_INS
WREC_DEL
WREC_UPD
RESET
MODE
MES_READ
REC_FIN
VALUE1
VALUE2
VALUE3
VALUE4
VALUE4B
VALUE5
VALUE6
216
Description
Sampling time [s]
Number of startup cycles
ID of the block
Archive name
Archive number
Record number in the user archive
Batch name
Batch ID
Number of repetitions if an error occurs;
Exception: The job is not repeated after in‐
serting (WREQ_INS).
Monitoring time for write job
Feedback structure from "FB_UA_WM"
Trigger Insert data record
Trigger Delete data record
Trigger Update data record
1 = Reset write interface
Currently not used (operating mode of the
block)
1 = Release for MES system
for reading data
0 = No read release for MES system for
reading data
1 = Recording / changes to data record
completed
0 = Archive data record recording / change
Example: Archive value 1
Example: Archive value 2
Example: Archive value 3
Example: Archive value 4 part A
Example: Archive value 4 part B
Example: Archive value 5
Example: Archive value 6
Type
REAL
1
INT
10
INT
0
STRING[16]
''
DINT
0
DINT
0
STRING[32]
''
DWORD
0
INT
1
REAL
30.0
UDT_UA_W_ST
BOOL
0
BOOL
0
BOOL
0
BOOL
0
WORD
0
BOOL
0
BOOL
0
DINT
0
REAL
0.0
STRING[16]
''
DWORD
16#08123123
DWORD
16#59590000
BOOL
0
DINT
0
Advanced Process Functions (APF)
Function Manual, 07/2016, A5E38719883-AA
Default
WinCC tag
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-

Advertisement

Table of Contents
loading

Table of Contents