ACT_DESC
ACT_BDT1 ACT_BDT2
ACT_ORIG
ACT_SDT1 ACT_SDT2
ACT_STAT
ACTSTATE
Once the job has ended, the job data from the job interface are saved and supplemented with
the end time, and are then available at the following outputs for further processing:
LAS_TITL
LAS_ID
LAS_PNO
LAS_SP
LAS_AVAL
LAS_DES
LAS_BDT1
LAS_BDT2
LAS_ORI
LAS_SDT1
LAS_SDT2
LAS_EDT1
LAS_EDT2
LAS_STAT
LASSTATE
Automatic specifications
● Job title
You can activate "automatic job title specification" mode at the AS "MODE" input.
"QREQ_TL" = 1 at the AS output triggers a job title request. The job title specified at the
"TLIN" input is applied with a positive edge at the "ACC_TLIN" input.
● Job ID
You can activate "automatic ID specification" mode at the AS "MODE" input. "QREQ_ID"
= 1 at the AS output triggers a job ID request. The job ID specified at the "IDIN" input is
applied with a positive edge at the "ACC_IDIN" input.
Advanced Process Functions (APF)
Function Manual, 07/2016, A5E38719883-AA
Output
Description
Time of creation
Creator
Start time
With bit 0 = 1 "reference quantity"
Bit 0
1 = An "FB_ERROR" (AS input) has occurred during job execution
Bit 1
1 = A control system error has occurred during job execution
Bit 5
1 = Job completed normally
Bit 6
1 = Job completed after "END" selected
Bit 7
1 = Job ended with "Abort"
Output
Job title
Job ID
Parameter set
Setpoint
Actual value
Description
Time of creation
Creator
Start time
End time
With bit 0 = 1 "reference quantity"
Bit 0
1 = "FB_ERROR" (AS input) occurred during job execution
Bit 1
1 = Control system error occurred during job execution
Bit 5
1 = Job completed normally
Bit 6
1 = Job completed after "END" selected
Bit 7
1 = Job ended with "Abort"
Order management
Meaning
Meaning