I/Os - Siemens SIMATIC PCS 7 Function Manual

Process control system, advanced process functions apf
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

11
12
13
14
15
Automatic repetition of jobs
The "COUNT" input value defines how often a job is to be repeated if an error occurs (COUNT
= 0 -> no repetition). Until the specified number of job repetitions has been reached, the job is
reactivated by FB_STOR after a wait cycle.
An error message is output after the last repetition.
A new job is only possible if the request signal at the request inputs "L_REC_R" and
"L_REC_W" is set again.
5.1.4

I/Os

Input parameters
The following table shows the input parameters of the "FB_STOR" block:
Parameter
SAMPLE_T
Sampling time [s]
RUNUPCYC
Number of startup cycles
ID
ID of the block
ARCH_NA
Archive name
REC_ID
Data record number in user archive
FORMAT
Data format content 0 = DINT, >1 = REAL
BA_NA
Batch name
BA_ID
Batch ID
COUNT
Number of repetitions of the send or read job if an error
occurs
INIREP_T
Delay time for repetition of initialization if an error oc‐
curs
TIME_MON
Read/write job monitoring time
TRIGMODE
Trigger mode for automatically sending current proc‐
ess values
R_REC_ST
Input structure with job feedback from FB_UA_RM
W_REC_ST
Input structure with job feedback from FB_UA_WM
L_REC_R
Interconnectable input: 1 = Read data request
Advanced Process Functions (APF)
Function Manual, 07/2016, A5E38719883-AA
Bit
Monitored input
REL4DYN
Not used
Not used
Not used
None (restart)
Description
Storage location management
5.1 FB_STOR (FB_STORI, FB_STORR)
Meaning
Dynamic procedure enable 4
-
-
-
Read data upon CPU restart
Type
De-
fault
REAL
1
INT
10
INT
0
STRING[16]
''
DINT
0
DINT
STRING[32]
''
DWORD
0
INT
1
REAL
600.0
REAL
30.0
WORD
0
UDT_UA_R_S
T
UDT_UA_W_
ST
BOOL
0
WinCC tag
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
69

Advertisement

Table of Contents
loading

Table of Contents