YASKAWA A1000 Series Quick Start Manual page 86

High performance vector control drive
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

4 Start-Up Programming & Operation
The output signal range can be selected between 0 to +10 Vdc or -10 to +10 Vdc using parameter H4-07 and H4-08.
Figure 73
illustrates how gain and bias settings work.
No.
H4-02
Multi-Function Analog Output Terminal FM Gain
H4-03
Multi-Function Analog Output Terminal FM Bias
H4-05
Multi-Function Analog Output Terminal AM Gain
H4-06
Multi-Function Analog Output Terminal AM Bias
Using Gain and Bias to Adjust Output Signal Level
When viewing a gain setting parameter (H4-02 or H4-05) on the digital operator, the analog output will supply a voltage
signal equal to 100% of the monitor value (including changes made from bias and gain settings). When viewing a bias
setting parameter (H4-03 or H4-06), the analog output voltage will supply a signal equal to 0% monitor value (including
changes made from bias and gain settings).
Example 1: To have an output signal of 5 V at terminal FM when the monitored value is at 100%, set H4-02 to 50%.
Example 2: To have an output signal of 10 V at terminal FM when the monitored value is at 76.7%, set H4-02 to 150%.
Figure 73
10 V
Output Voltage
5 V
0 V
0%
Example 3: To have an output signal of 3 V at terminal FM when the monitored value is at 0%, set H4-03 to 30%.
Figure 74
10 V
Output Voltage
3 V
0 V
0%
86
Name
H4-07, 08 = 0
Gain 150%
Bias 0%
Gain 100%
Bias 0%
Gain 50%
Bias 0%
100%
Monitor Value
Figure 73 Analog Output Gain and Bias Setting Example 1 and 2
H4-07, 08 = 0
Bias 30%
Gain 100%
Bias 0%
Gain 100%
100%
Monitor Value
Figure 74 Analog Output Gain and Bias Setting Example 3
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
H4-07, 08 = 1
15 V
Output Voltage
10 V
5 V
-100%
100%
Monitor Value
-5 V
-10 V
-15 V
H4-07, 08 = 1
15 V
Output Voltage
10V
5 V
-100%
100%
Monitor Value
-5 V
-10 V
-15 V
Default
100.0%
0.0%
50.0%
0.0%
Gain = 150%
Bias = 0%
Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%
Gain = 100%
Bias = 30%
Gain = 100%
Bias = 0%
YEC_common