YASKAWA A1000 Series Quick Start Manual page 27

High performance vector control drive
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

Figure 10
Wiring sequence should shut off
power to the drive when a fault
<14>
output is triggered.
ELCB (MCCB)
R
Three-phase
power supply
S
200 to 240 V
T
50 / 60 Hz
MC
MB
2MCCB
THRX
OFF
ON
MC
SA
MC
Braking resistor unit
Thermal relay trip contact
THRX
1
2
SA
TRX
SA
MC MA
TRX
Fault relay
contact
Multi-function
digtial inputs
(default setting)
Multi-function
analog/ pulse
train inputs
Safety
switch
S 2
S 1
Open
Safety relay /
controller
Figure 10 Drive Standard Connection Diagram (example: CIMR-A 2A0040)
<1> Remove the jumper when installing a DC reactor. Models CIMR-A 2A0110 through 2A0415 and 4A0058 through 4A0675 come with a
built-in DC reactor.
<2> When installing a dynamic braking option, a thermal relay sequence should also be set up to shut off power to the drive in case overheat
occurs.
<3> The drive's protection function for the internal braking transistor needs to be disabled (L8-55 = 0) if using a regen unit such as a regen
converter or some type of dynamic braking options (and therefore not the internal braking transistor). If left enabled, a braking resistor fault
(rF) may result. Make sure Stall Prevention is disabled (L3-04 = 0) whenever using a regenerative converter, a regenerative unit or a dynamic
braking option. If left enabled, the drive may not stop within the specified deceleration time.
<4> Self-cooling motors do not require wiring that would be necessary with motors using a cooling fan.
<5> Supplying power to the control circuit separately from the main circuit requires a 24 V power supply (option).
<6> For control modes that do not use a motor speed feedback signal, PG option card wiring is not necessary.
<7> This figure shows an example of a sequence input to S1 through S8 using a non-powered relay or an NPN transistor. Use jumper S3 to select
sink or source, and an internal or external power supply.
<8> The maximum output current capacity for the +V and -V terminals on the control circuit is 20 mA. Never short terminals +V, -V, and AC, as
this can cause erroneous operation or damage the drive.
<9> Set DIP switch S1 to select between a voltage or current input signal to terminal A2. The default setting is for current input.
<10> Enable the termination resistor in the last drive in a MEMOBUS network by setting DIP switch S2 to the ON position.
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
Terminals -, +1, +2, B1, B2 are
DC reactor
for connection options. Never
connect power supply lines to
these terminals
U
U
2MCCB
r1
s1
+
+
t1
2
Fuse
MC
R/L1
S/L2
T/L3
If running from a 400 V power
supply, a step-down transformer
is needed to reduce the voltage
to 200 V.
Forward Run / Stop
S 1
Reverse Run / Stop
S 2
External fault
S 3
Fault reset
S 4
Multi-speed step 1
S 5
Multi-speed step 2
S 6
Jog speed
S 7
External Baseblock
S 8
SC
Shield ground terminal
RP
Pulse Train Input (max 32 kHz)
<8>
+
V
Power supply +10.5 Vdc, max. 20 mA
2 k Ω
A 1
Analog Input 1
(Frequency Reference Bias)
0 to +10 Vdc (20 kΩ)
A 2
Analog Input 2
(Frequency Reference Bias)
0 to +10 Vdc (20 kΩ)
4 to 20 mA / 0 to 20 mA (250 Ω)
A 3
Analog Input 3
(Aux. frequency reference)
AC
0 to +10 Vdc (20 kΩ)
0 V
<8>
V
Power supply, -10.5 Vdc, max. 20 mA
Termination resistor
(120 Ω, 1/2 W)
+
+
R
R
+
+
MEMOBUS/Modbus
S
comm. RS485/422
max. 115.2 kBps
S
IG
Safe Disable inputs
H 1
<11>
H 2
Wire
jumper
<12>
HC
<1>
Thermal relay
(option)
<2>
(option)
X
X
Braking resistor
Jumper
<3>
(option)
+
+
1
B 1
B 2
U/T 1
Main Circuit
V/T 2
Drive
W/T
<5>
Control Circuit
TB1
PG B3
<6>
A+
A
B+
B
Z+
Z
SD
FE
TB2
IP
IG
AO
IG
BO
Sink / Source mode
IG
selection jumper S3
ZO
<7>
(default: Sink)
IG
CN5-C
Option board
+
24 V
connectors
CN5-B
MA
CN5-A
MB
MC
M 1
M 2
DIP Switch S1
V
I
P 1
<9>
P 2
PC
MP
AC
DIP
Switch S2
0 V
FM
<10>
AM
AC
0 V
E (G)
DM
DM
3 Electrical Installation
<4>
FU
r1
FV
s1
M
FW
t1
Cooling fan
U
V
M
W
3
YEC_common
Ground
PG
A track monitor
B track monitor
Fault relay output
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function relay output
(During Run)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function photo coupler output 1
(Zero Speed)
48 Vdc, max 50 mA
Multi-function photo coupler output 2
(Speed Agree 1)
48 Vdc, max 50 mA
Multi-function pulse train output
(Output frequency)
0 to 32 kHz (2.2 kΩ)
Multi-function analog output 1
+
+
(Output frequency)
FM
-10 to +10 Vdc (2mA)
<13>
Multi-function analog output 2
+
+
(Output current)
AM
-10 to +10 Vdc (2mA)
<13>
EDM
+
+
(Safety Electronic Device Monitor)
shielded line
twisted-pair shielded line
control circuit terminal
main circuit terminal
3
27

Advertisement

Table of Contents
loading

Table of Contents