<29> The setting range varies according to the motor code entered to E5-01 when using OLV/PM. The setting range is 0.0 to 400.0 Hz when E5-01
is set to FFFFH.
<30> The setting value is F in OLV.
<44> The default value shown here is for the following localized drives: Japan (Model code: CIMR-AA A), Asia (Model code: CIMR-AT A)
For default value of China localized drive (Model code: CIMR-AB A), refer to the A1000 Technical Manual.
E2: Motor 1 Parameters
No.
Name
E2-01
Motor Rated Current
E2-02
Motor Rated Slip
E2-03
Motor No-Load Current
E2-04
Number of Motor Poles
Motor Line-to-Line
E2-05
Resistance
E2-06
Motor Leakage Inductance
Motor Iron-Core Saturation
E2-07
Coefficient 1
Motor Iron-Core Saturation
E2-08
Coefficient 2
E2-09
Motor Mechanical Loss
Motor Iron Loss for Torque
E2-10
Compensation
E2-11
Motor Rated Power
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<19> This value's number of decimal places depends on the drive model and the Heavy/Normal duty selection in parameter C6-01. The value will
have two decimal places (0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer to
and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW.
E3: V/f Pattern for Motor 2
These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 5, 6, 7).
No.
Name
Motor 2 Control Mode
E3-01
Selection
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
Sets the motor nameplate full load current in Amps. Automatically set during
Auto-Tuning.
Sets the motor rated slip. Automatically set during Auto-Tuning.
Sets the no-load current for the motor. Automatically set during Auto-Tuning.
Sets the number of motor poles. Automatically set during Auto-Tuning.
Sets the phase-to-phase motor resistance. Automatically set during
Auto-Tuning.
Sets the voltage drop due to motor leakage inductance as a percentage of motor
rated voltage. Automatically set during Auto-Tuning.
Sets the motor iron saturation coefficient at 50% of magnetic flux.
Automatically set during Auto-Tuning.
Sets the motor iron saturation coefficient at 75% of magnetic flux.
Automatically set during Auto-Tuning.
Sets the motor mechanical loss as a percentage of motor rated power (kW).
Sets the motor iron loss.
Sets the motor rated power in kilowatts (1 HP = 0.746 kW). Automatically set
during Auto-Tuning.
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
Description
Description
B Parameter List
Setting
Default:
<9>
Min: 10% of drive
rated current
Max: 200% of drive
rated current
<19>
Default:
<9>
Min: 0.00 Hz
Max: 20.00 Hz
Default:
<9>
Min: 0 A
Max: E2-01
<19>
Default: 4
Min: 2
Max: 48
Default:
<9>
Min: 0.000 Ω
Max: 65.000 Ω
Default:
<9>
Min: 0.0%
Max: 40.0%
Default: 0.50
Min: E2-07
Max: 0.50
Default: 0.75
Min: E2-07
Max: 0.75
Default: 0.0%
Min: 0.0%
Max: 10.0%
Default:
<9>
Min: 0 W
Max: 65535 W
Default:
<9>
Min: 0.00 kW
Max: 650.00 kW
Table 60
and
Table
61)
Setting
Default: 0
Min: 0
Max: 3
B
145