3 Electrical Installation
Wire Size and Torque Specifications
Select appropriate wire type and gauges from
wire ends. Refer to
Table 14
Terminal
Terminal
Block
FM, AC, AM, P1,
P2, PC, SC, A1,
A2, A3, +V, -V,
S1-S8, MA, MB,
TB1, TB2
MC, M1, M2
E (G)
HC, H1, H2,
TB4, TB5,
DM+, DM-, IG,
TB6
R+, R-, S+, S-, RP,
MP
Ferrule-Type Wire Terminals
Prepare wire ends with insulated sleeves before connecting to the drive. See
recommends CRIMPFOX ZA-3, a crimping tool manufactured by PHOENIX CONTACT.
Figure 34
Size mm
(AWG)
2
0.25 (24)
0.34 (22)
0.5 (20)
Wiring the Control Circuit Terminal
This section describes the proper procedures and preparations for wiring the control terminals.
WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply could
result in death or serious injury.
NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3, -, +1, +2) and
other high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference.
NOTICE: Separate wiring for digital output terminals MA, MB and MC from wiring to other control circuit lines. Improper wiring
practices could result in drive or equipment malfunction or nuisance trips.
NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper application of peripheral
devices could result in drive performance degradation due to improper power supply.
NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices
could result in drive or equipment malfunction due to short circuit.
NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in drive
or equipment malfunction or nuisance trips.
46
Table
for ferrule terminal types and sizes.
Table 13 Wire Gauges and Torque Specifications
Tightening
Applicable wire
Screw
Torque
Size
N m
(lb.in.)
0.8 to 1.0
M3.5
(7.1 to 8.6)
(20 to 14)
0.8 to 1.0
M3.5
(7.1 to 8.6)
(20 to 14)
Standard 0.25 to
0.22 to 0.25
M2
(24 to 17)
(1.9 to 2.2)
Single 0.25 to 1.5
(24 to 16)
Figure 34 Ferrule Dimensions
Table 14 Ferrule Terminal Types and Sizes
Type
L (mm)
AI 0.25-6YE
10.5
AI 0.34-6TQ
10.5
AI 0.5-6WH
14
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
13. For simpler and more reliable wiring, use crimp ferrules on the
Bare Wire Terminal
Recomm.
size
mm
2
mm
2
(AWG)
(AWG)
0.5 to 2
0.75
(18)
0.5 to 2
1.25
(12)
1.0
0.75
(18)
d1
YEC_common
d2
d1 (mm)
d2 (mm)
0.8
2
0.8
2
1.1
2.5
Ferrule-Type Terminal
Applicable wire
size
Recomm.
mm
mm
(AWG)
2
2
(AWG)
0.25 to 0.5
0.5
(24 to 20)
(20)
Table 14
for dimensions. Yaskawa
Manufacturer
PHOENIX CONTACT
Wire Type
Shielded line,
etc.