YASKAWA A1000 Series Quick Start Manual page 159

High performance vector control drive
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

No.
Name
Terminal A3 Signal Level
H3-05
Selection
Terminal A3 Function
H3-06
Selection
H3-07
Terminal A3 Gain Setting
H3-08
Terminal A3 Bias Setting
H3-09
Terminal A2 Signal Level
Selection
Terminal A2 Function
H3-10
Selection
H3-11
Terminal A2 Gain Setting
H3-12
Terminal A2 Bias Setting
H3-13
Analog Input Filter Time
Constant
Analog Input Terminal
H3-14
Enable Selection
H3-
Function
Setting
0
Frequency Bias
1
Frequency Gain
Auxiliary Frequency Reference 1 (used
2
as a Multi-Step Speed 2)
Auxiliary Frequency Reference 2 (3rd
3
step analog)
4
Output Voltage Bias
5
Accel/Decel Time Gain
6
DC Injection Braking Current
Overtorque/Undertorque Detection
7
Level
8
Stall Prevention Level During Run
9
Output Frequency Lower Limit Level
B
PID Feedback
C
PID Setpoint
D
Frequency Bias
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
0: 0 to 10 V
1: –10 to 10 V
Sets the function of terminal A3.
Sets the level of the input value selected in H3-06 when 10 V is input at terminal
A3.
Sets the level of the input value selected in H3-06 when 0 V is input at terminal
A3.
0: 0 to 10 V
1: –10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use DIP switch S1 to set input terminal A2 for a current or a voltage input
signal.
Sets the function of terminal A2.
Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input at
terminal A2.
Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is input
at terminal A2.
Sets a primary delay filter time constant for terminals A1, A2, and A3. Used for
noise filtering.
Determines which of the analog input terminals will be enabled when a digital
input programmed for "Analog input enable" (H1-
1: Terminal A1 only
2: Terminal A2 only
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
H3 Multi-Function Analog Input Settings
10 V = E1-04 (maximum output frequency)
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting of -100 to
0%.
10 V = E1-04 (maximum output frequency)
10 V = E1-04 (maximum output frequency)
10 V = E1-05 (motor rated voltage)
10 V = 100%
10 V = Drive rated current
10 V = Drive rated current (V/f, V/fw/PG)
10 V = Motor rated torque (OLV, CLV, OLV/PM, AOLV/PM, CLV/PM)
10 V = Drive rated current
10 V = E1-04 (maximum output frequency)
10 V = 100%
10 V = 100%
10 V = E1-04 (maximum output frequency)
Description
= C) is activated.
Description
B Parameter List
Setting
Default: 0
Min: 0
Max: 1
Default: 2
Min: 0
Max: 31
Default: 100.0%
Min: -999.9%
Max: 999.9%
Default: 0.0%
Min: -999.9%
Max: 999.9%
Default: 2
Min: 0
Max: 3
Default: 0
Min: 0
Max: 31
Default: 100.0%
Min: -999.9%
Max: 999.9%
Default: 0.0%
Min: -999.9%
Max: 999.9%
Default: 0.03 s
Min: 0.00 s
Max: 2.00 s
Default: 7
Min: 1
Max: 7
B
159

Advertisement

Table of Contents
loading