B Parameter List
No.
Name
Motor 2 Maximum Output
E3-04
Frequency
E3-05
Motor 2 Maximum Voltage
E3-06
Motor 2 Base Frequency
Motor 2 Mid Output
E3-07
Frequency
Motor 2 Mid Output
E3-08
Frequency Voltage
Motor 2 Minimum Output
E3-09
Frequency
Motor 2 Minimum Output
E3-10
Frequency Voltage
Motor 2 Mid Output
E3-11
Frequency 2
E3-12
Motor 2 Mid Output
Frequency Voltage 2
<24>
E3-13
Motor 2 Base Voltage
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<24> Parameter ignored when E3-11 (Motor 2 Mid Output Frequency 2) and E3-12 (Motor 2 Mid Output Frequency Voltage 2) are set to 0.
<25> Default setting depends on the control mode for motor 2 set in parameter E3-01. The value shown here is for V/f Control.
<26> The setting range is 0.0 to 66.0 in AOLV/PM.
<27> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<44> The default value shown here is for the following localized drives: Japan (Model code: CIMR-AA A), Asia (Model code: CIMR-AT A).
For default value of China localized drive (Model code: CIMR-AB A), refer to the A1000 Technical Manual.
E4: Motor 2 Parameters
These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 5, 6, 7).
No.
Name
E4-01
Motor 2 Rated Current
E4-02
Motor 2 Rated Slip
Motor 2 Rated No-Load
E4-03
Current
E4-04
Motor 2 Motor Poles
Motor 2 Line-to-Line
E4-05
Resistance
146
These parameters are only applicable when E1-03 is set to F.
To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this
case, the setting for E3-08 will be disregarded. Ensure that the four frequencies
are set according to these rules or an oPE10 fault will occur:
E3-09 ≤ E3-07 < E3-06 ≤ Ε3−11 ≤ E3-04
Output Voltage (V)
E3-05
E3-12
E3-13
E3-08
E3-10
Note: E3-07 and E3-08 are only available in the following control modes: V/f,
V/f w/PG and OLV.
Sets the full load current for motor 2. Automatically set during Auto-Tuning.
Sets the rated slip for motor 2. Automatically set during Auto-Tuning.
Sets the no-load current for motor 2. Automatically set during Auto-Tuning.
Sets the number of poles of motor 2. Automatically set during Auto-Tuning.
Sets the phase-to-phase resistance for motor 2. Automatically set during
Auto-Tuning.
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
Description
E3-09
E3-07 E3-06 E3-11 E3-04
Frequency (Hz)
Description
Setting
Default:
<25> <44>
Min: 40.0
Max: 400.0
Default:
<18>
Min: 0.0 V
Max: 255.0 V
<18>
Default:
<25> <44>
Min: 0.0
Max: E3-04
Default:
<25> <44>
Min: 0.0
Max: E3-04
Default:
<18> <25>
Min: 0.0 V
Max: 255.0 V
<18>
Default:
<25> <44>
Min: 0.0
Max: E3-04
Default:
<18> <25>
Min: 0.0 V
Max: 255.0 V
<18>
Default: 0.0
<24>
Min: 0.0
Max: E3-04
<26>
Default: 0.0 V
<18>
Min: 0.0 V
Max: 255.0 V
<18>
Default: 0.0 V
<18> <27>
Min: 0.0 V
Max: 255.0 V
<18>
Setting
Default:
<9>
Min: 10% of drive
rated current
Max: 200% of drive
rated current
<19>
Default:
<9>
Min: 0.00 Hz
Max: 20.00 Hz
<19>
Default:
<9>
Min: 0 A
Max: E4-01
<19>
Default: 4
Min: 2
Max: 48
Default:
<9>
Min: 0.000 Ω
Max: 65.000 Ω