B Parameter List
No.
Name
b5-39
PID Setpoint Display Digits
Frequency Reference
b5-40
Monitor Content during PID
<5> Default setting is dependent on PID setpoint scaling (b5-20).
b6: Dwell Function
No.
Name
b6-01
Dwell Reference at Start
b6-02
Dwell Time at Start
b6-03
Dwell Reference at Stop
b6-04
Dwell Time at Stop
b7: Droop Control
No.
Name
b7-01
Droop Control Gain
b7-02
Droop Control Delay Time
b8: Energy Saving
No.
Name
Energy Saving Control
b8-01
Selection
b8-02
Energy Saving Gain
b8-03
Energy Saving Control Filter
Time Constant
Energy Saving Coefficient
b8-04
Value
b8-05
Power Detection Filter Time Sets a time constant filter for output power detection.
Search Operation Voltage
b8-06
Limit
<4> Default setting is dependent on the control mode (A1-02), the drive model (o2-04), and the Drive Duty (C6-01).
<8> Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<10> Default setting is determined by the control mode (A1-02).
136
0: No decimal places
1: One decimal places
2: Two decimal places
3: Three decimal places
0: Display the frequency reference (U1-01) after PID compensation has been
added.
1: Display the frequency reference (U1-01) before PID compensation has been
added.
Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain
that frequency at start.
Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain
that frequency at stop.
Sets the speed reduction gain applied at a torque reference of 100%. Set as a
percentage of motor base speed.
Used to adjust the responsiveness of Droop Control.
0: Disabled
1: Enabled
Sets the gain used for Energy Saving.
Sets a time constant for Energy Saving.
Determines the level of maximum motor efficiency. Setting range is 0.0 to
2000.0 maximum output up to 3.7 kW. The display resolution depends on the
rated output power of the drive after the Drive Duty has been set in parameter
C6-01. Refer to
Model Number and Nameplate Check on page
Sets the limit for the voltage search operation as a percentage of the motor rated
voltage.
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
Description
Description
Description
Description
Setting
Default:
<5>
Min: 0
Max: 3
Default: 0
Min: 0
Max: 1
Setting
Default: 0.0 Hz
Min: 0.0 Hz
Max: 400.0 Hz
Default: 0.0 s
Min: 0.0 s
Max: 10.0 s
Default: 0.0 Hz
Min: 0.0 Hz
Max: 400.0 Hz
Default: 0.0 s
Min: 0.0 s
Max: 10.0 s
Setting
Default: 0.0%
Min: 0.0%
Max: 100.0%
Default: 0.05 s
Min: 0.03 s
Max: 2.00 s
Setting
Default:
<10>
Min: 0
Max: 1
Default:
<10>
Min: 0.0
Max: 10.0
Default:
<4>
Min: 0.00 s
Max: 10.00 s
Default:
<8> <9>
Min: 0.00
Max: 655.00
17.
Default: 20 ms
Min: 0 ms
Max: 2000 ms
Default: 0%
Min: 0%
Max: 100%