YASKAWA A1000 Series Quick Start Manual page 171

High performance vector control drive
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

No.
Name
User Parameter Default
o2-03
Value
o2-04
Drive Model Selection
Frequency Reference Setting
o2-05
Method Selection
Operation Selection when
o2-06
Digital Operator is
Disconnected
Motor Direction at Power Up
o2-07
when Using Operator
o2-09
Reserved
o3: Copy Function
No.
Name
o3-01
Copy Function Selection
o3-02
Copy Allowed Selection
o4: Maintenance Monitor Settings
No.
Name
Cumulative Operation Time
o4-01
Setting
Cumulative Operation Time
o4-02
Selection
Cooling Fan Operation Time
o4-03
Setting
Capacitor Maintenance
o4-05
Setting
DC Bus Pre-Charge Relay
o4-07
Maintenance Setting
o4-09
IGBT Maintenance Setting
o4-11
U2, U3 Initialization
o4-12
kWh Monitor Initialization
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
0: No change.
1: Set defaults. Saves parameter settings as default values for a User
Initialization.
2: Clear all. Clears the default settings that have been saved for a User
Initialization.
Enter the drive model. Setting required only if installing a new control board.
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be adjusted using
the up and down arrow keys only.
0: The drive continues operating if the digital operator is disconnected.
1: A fault is triggered (oPr) and the motor coasts to stop.
0: Forward
1: Reverse
This parameter requires that drive operation be assigned to the digital operator.
0: No action
1: Read parameters from the drive, saving them onto the digital operator.
2: Copy parameters from the digital operator, writing them to the drive.
3: Verify parameter settings on the drive to check if they match the data saved on
the operator.
0: Read operation prohibited
1: Read operation allowed
Sets the value for the cumulative operation time of the drive in units of 10 h.
0: Logs power-on time
1: Logs operation time when the drive output is active (output operation time).
Sets the value of the fan operation time monitor U4-03 in units of 10 h.
Sets the value of the Maintenance Monitor for the capacitors. See U4-05 to
check when the capacitors may need to be replaced.
Sets the value of the Maintenance Monitor for the soft charge bypass relay. See
U4-06 to check when the bypass relay may need to be replaced.
Sets the value of the Maintenance Monitor for the IGBTs. See U4-07 to check
when the IGBTs may need to be replaced.
0: U2-
and U3-
monitor data is not reset when the drive is initialized
(A1-03).
1: U2-
and U3-
monitor data is reset when the drive is initialized (A1-
03).
0: U4-10 and U4-11 monitor data is not reset when the drive is initialized (A1-
03).
1: U4-10 and U4-11 monitor data is reset when the drive is initialized (A1-03).
Description
Description
Description
B Parameter List
Setting
Default: 0
Min: 0
Max: 2
Default:
Determined by
drive capacity
Min: –
Max: –
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1
Setting
Default: 0
Min: 0
Max: 3
Default: 0
Min: 0
Max: 1
Setting
Default: 0 h
Min: 0 h
Max: 9999 h
Default: 0
Min: 0
Max: 1
Default: 0 h
Min: 0 h
Max: 9999 h
Default: 0%
Min: 0%
Max: 150%
Default: 0%
Min: 0%
Max: 150%
Default: 0%
Min: 0%
Max: 150%
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1
B
171