YASKAWA A1000 Series Quick Start Manual page 161

High performance vector control drive
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

No.
Name
Communication Parity
H5-03
Selection
Stopping Method After
H5-04
Communication Error (CE)
Communication Fault
H5-05
Detection Selection
H5-06
Drive Transmit Wait Time
H5-07
RTS Control Selection
H5-09
CE Detection Time
Unit Selection for
H5-10
MEMOBUS/Modbus
Register 0025H
Communications ENTER
H5-11
Function Selection
Run Command Method
H5-12
Selection
<32> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
H6: Pulse Train Input/Output
No.
Name
Pulse Train Input Terminal
H6-01
RP Function Selection
H6-02
Pulse Train Input Scaling
H6-03
Pulse Train Input Gain
H6-04
Pulse Train Input Bias
H6-05
Pulse Train Input Filter Time Sets the pulse train input filter time constant.
H6-06
Pulse Train Monitor
Selection
H6-07
Pulse Train Monitor Scaling
Pulse Train Input Minimum
H6-08
Frequency
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
0: No parity
1: Even parity
2: Odd parity
Cycle power for the setting to take effect.
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
0: Disabled
1: Enabled. If communication is lost for more than two seconds, a CE fault will
occur.
Set the wait time between receiving and sending data.
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
Sets the time required to detect a communications error. Adjustment may be
needed when networking several drives.
0: 0.1 V units
1: 1 V units
0: Drive requires an Enter command before accepting any changes to parameter
settings.
1: Parameter changes are activated immediately without the Enter command
(same as V7).
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV
0: Frequency reference
1: PID feedback value
2: PID setpoint value
3: V/f Control with Simple PG feedback (possible only when using motor 1 in
V/f Control)
Sets the terminal RP input signal frequency that is equal to 100% of the value
selected in H6-01.
Sets the level of the value selected in H6-01 when a frequency with the value set
in H6-02 is input.
Sets the level of the value selected in H6-01 when 0 Hz is input.
Select the pulse train monitor output function (value of the
U -
).
Example: To select U5-01, set "501".
Sets the terminal MP output signal frequency when the monitor value is 100%.
To have the pulse train monitor output equal the output frequency, set H6-06 to 2
and H6-07 to 0.
Sets the minimum frequency for the pulse train input to be detected. Enabled
when H6-01 = 0, 1, or 2.
Description
Description
-
B Parameter List
Setting
Default: 0
Min: 0
Max: 2
Default: 0
Min: 0
Max: 3
Default: 0
Min: 0
Max: 1
Default: 5 ms
Min: 5 ms
Max: 65 ms
Default: 1
Min: 0
Max: 1
Default: 2.0 s
Min: 0.0 s
Max: 10.0 s
Default: 0
Min: 0
Max: 1
Default: 1
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1
Setting
Default: 0
Min: 0
Max: 3
Default: 1440 Hz
Min: 1000 Hz
Max: 32000 Hz
Default: 100.0%
Min: 0.0%
Max: 1000.0%
Default: 0.0%
Min: -100.0%
Max: 100.0%
Default: 0.10 s
Min: 0.00 s
Max: 2.00 s
part of
Default: 102
Min: 000
Max: 809
Default: 1440 Hz
Min: 0 Hz
Max: 32000 Hz
Default: 0.5 Hz
Min: 0.1 Hz
Max: 1000.0 Hz