1.5 b: Application

1.5

b: Application

b1: Operation Mode Selection

No.
Name
(Hex.)
b1-01
Frequency Reference
Selection 1
(0180)
b1-02
Run Command Selection
1
(0181)
b1-03
Stopping Method
Selection
(0182)
b1-04
Reverse Operation
Selection
(0183)
b1-05
Operation Below
Minimum Freq
(0184)
b1-06
Digital Input Reading
(0185)
b1-07
LOCAL/REMOTE Run
Selection
(0186)
b1-08
Run Command Select in
PRG Mode
(0187)
b1-09
LOCAL/REMOTE Select
during RUN
(0188)
Expert
22
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input method for the frequency reference.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
4 : Pulse Train Input
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : Memobus/Modbus Communications
3 : Option PCB
V/f
CL-V/f
OLV
CLV
AOLV
Sets the method to stop the motor after removing a Run command or entering a Stop
command.
Note:
When A1-02 = 3, 4, 5, 6, 7, 8 [Control Method Selection = CLV, AOLV, OLV/PM,
AOLV/PM, CLV/PM, EZOLV], the setting range is 0, 1, 3.
0 : Ramp to Stop
1 : Coast to Stop
2 : DC Injection Braking to Stop
3 : Coast to Stop with Timer
V/f
CL-V/f
OLV
CLV
AOLV
Sets the reverse operation function. Disable reverse operation in fan or pump applications
where reverse rotation is dangerous.
0 : Reverse Enabled
1 : Reverse Disabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive operation when the frequency reference decreases to less than the value set
in E1-09 [Minimum Output Frequency].
0 : Operate at Frequency Reference
1 : Baseblock (Motor Coasts)
2 : Operate at Minimum Frequency
3 : Operate at Zero Speed
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of times that the drive reads the sequence input command to prevent
malfunction because of noise.
0 : Single Scan
1 : Double Scan
V/f
CL-V/f
OLV
CLV
AOLV
Sets drive response to an existing Run command when the drive receives a second Run
command from a different location.
0 : Disregard Existing RUN Command
1 : Accept Existing RUN Command
V/f
CL-V/f
OLV
CLV
AOLV
Sets the conditions for the drive to accept a Run command entered from an external source
when using the keypad to set parameters.
0 : Disregard RUN while Programming
1 : Accept RUN while Programming
2 : Allow Programming Only at Stop
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that lets you use the
and REMOTE Modes.
0 : Disabled
1 : Enabled
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
during operation to switch between LOCAL
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
Ref.
(Setting Range)
1
194
(0 - 4)
1
196
(0 - 3)
0
197
(0 - 3)
0
200
(0, 1)
0
200
(0 - 3)
1
201
(0, 1)
0
202
(0, 1)
0
202
(0 - 2)
0
203
(0, 1)

Advertisement