T2: Pm Motor Auto-Tuning - YASKAWA GA800 Programming Manual

Ac drive for industrial applications
Table of Contents

Advertisement

No.
Name
(Hex.)
T1-12
Test Mode Selection
(0BDB)
T1-13
No-load voltage
(0BDC)

T2: PM Motor Auto-Tuning

No.
Name
(Hex.)
T2-01
PM Auto-Tuning
Selection
(0750)
T2-02
PM Motor Code Selection
(0751)
T2-03
PM Motor Type
(0752)
T2-04
PM Motor Rated Power
(0730)
T2-05
PM Motor Rated Voltage
(0732)
T2-06
PM Motor Rated Current
(0733)
T2-07
PM Motor Base
Frequency
(0753)
T2-08
Number of PM Motor
Poles
(0734)
T2-09
PM Motor Base Speed
(0731)
T2-10
PM Motor Stator
Resistance
(0754)
T2-11
PM Motor d-Axis
Inductance
(0735)
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to enable Test Mode after Stationary Auto-Tuning. When you can operate
the motor with a light load attached after Stationary Auto-Tuning is complete, enable this
parameter.
Note:
You must first set T1-10 [Motor Rated Slip Frequency] = 0 Hz to enable this
parameter.
0 : No
1 : Yes
V/f
CL-V/f
OLV
CLV
AOLV
Sets the no-load voltage of the motor. If you know the no-load voltage at the rated speed in
a test report, set that voltage value. If you do not know the no-load voltage, do not change
from the initial value.
Note:
• To get the same qualities as a Yaskawa 1000-series drive or previous models, set this
parameter = T1-03 [Motor Rated Voltage] value.
• The default value is different for different models.
–2004 - 2008, 4002 - 4004: T1-03 × 0.85
–2010 - 2415, 4005 - 4302: T1-03 × 0.90
–4371- 4720: T1-03 × 0.95
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the type of Auto-Tuning for PM motors.
0 : Manual Entry w/ Motor Data Sheet
1 : Stationary (Ld, Lq, R)
2 : Stationary (R Only)
3 : Z-Pulse Offset (Pole Position)
4 : Rotational (Ld, Lq, R, back-EMF)
5 : High Frequency Injection
V/f
CL-V/f
OLV
CLV
AOLV
If the drive is operating a Yaskawa PM motor from the SMRA, SSR1, or SST4 series,
enter the PM motor code in accordance with the rotation speed and motor output.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the type of PM motor the drive will operate.
0 : IPM motor
1 : SPM motor
V/f
CL-V/f
OLV
CLV
AOLV
Uses the units set in o1-58 [Motor Power Unit Selection] to set the PM motor rated output
power.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated voltage (V) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated current (A) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the base frequency (Hz) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of motor poles.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor base speed (min
-1
(r/min)).
V/f
CL-V/f
OLV
CLV
AOLV
Sets the stator resistance for each motor phase.
Note:
This parameter does not set line-to-line resistance.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the d-axis inductance of the motor on a per phase basis.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
1.16 T: Motor Tuning
Default
Ref.
(Range)
0
535
(0, 1)
T1-03 × 0.85
535
(200 V Class: 0.0 - 255.0
V, 400 V Class: 0.0 -
510.0 V)
Default
Ref.
(Range)
0
535
(Determined by A1-02)
FFFF
536
(0000 - FFFF)
1
536
(0, 1)
Determined by o2-04,
536
C6-01
(0.00 - 650.00 HP)
200 V Class: 230.0 V, 400
536
V: 460.0 V
(200 V Class: 0.0 - 255.0
V, 400 V Class: 0.0 -
510.0 V)
Determined by o2-04
536
(10% to 200% of the
drive rated current)
60.0 Hz
536
(0.0 - 590.0 Hz)
4
537
(2 - 48)
-1
1750 min
(r/min)
537
(0 - 34500 min
-1
(r/min))
Determined by T2-02
537
(0.000 - 65.000 Ω)
Determined by T2-02
537
(0.00 - 600.00 mH)
109
1

Advertisement

Table of Contents
loading