B3: Speed Search - YASKAWA GA800 Programming Manual

Ac drive for industrial applications
Table of Contents

Advertisement

1.5 b: Application
No.
Name
(Hex.)
b2-13
Short Circuit Brake Time
@ Stop
(01BB)
b2-18
Short Circuit Braking
Current
(0177)

b3: Speed Search

No.
Name
(Hex.)
b3-01
Speed Search at Start
Selection
(0191)
b3-02
SpeedSearch Deactivation
Current
(0192)
b3-03
Speed Search
Deceleration Time
(0193)
b3-04
V/f Gain during Speed
Search
(0194)
b3-05
Speed Search Delay Time
(0195)
b3-06
Speed Estimation Current
Level 1
(0196)
Expert
b3-07
Speed Estimation Current
Level 2
(0197)
Expert
b3-08
Speed Estimation ACR P
Gain
(0198)
b3-09
Speed Estimation ACR I
Time
(0199)
b3-10
Speed Estimation
Detection Gain
(019A)
Expert
24
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Short Circuit Braking time at stop.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Short Circuit Braking Current as a percentage of the motor rated current.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor
rated current.
• A1-02 = 5, 6 [OLV/PM, AOLV/PM]: E5-03 [PM Motor Rated Current (FLA)]
• A1-02 = 8 [EZOLV]: E9-06 [Motor Rated Current (FLA)]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Speed Search at Start function where the drive will perform Speed Search with
each Run command.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the current level that stops Speed Search as a percentage of the drive rated output
current. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the deceleration time during Speed Search operation. Set the length of time to
decelerate from the maximum output frequency to the minimum output frequency.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this parameter takes effect
only in Expert Mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ratio used to reduce the V/f during searches to reduce the output current during
speed searches.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Speed Search delay time to activate a magnetic contactor installed between the
drive and motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level of current that flows to the motor during Speed Estimation Speed Search as a
coefficient of the motor rated current. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level of current that flows to the motor during Speed Estimation Speed Search as a
coefficient of E2-03 [Motor No-Load Current] or E4-03 [Motor 2 Rated No-Load
Current]. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the proportional gain for the automatic current regulator during Speed Estimation
Speed Search. Also adjusts speed search responsiveness. Usually it is not necessary to
change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the integral time for the automatic current regulator during Speed Estimation Speed
Search. Also adjusts speed search responsiveness. Usually it is not necessary to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain to correct estimated frequencies from Speed Estimation Speed Search.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
Ref.
(Range)
A1-02 = 8: 0.00 s
210
Other than A1-02 = 8:
0.50 s
(0.00 - 25.50 s)
100.0%
210
(0.0 - 200.0%)
Default
Ref.
(Range)
Determined by A1-02
214
(0, 1)
Determined by A1-02
214
(0 - 200%)
2.0 s
214
(0.1 - 10.0 s)
Determined by o2-04
215
(10 - 100)
0.2 s
215
(0.0 - 100.0 s)
Determined by o2-04
215
(0.0 - 2.0)
1.0
215
(0.0 - 3.0)
Determined by A1-02 and
215
o2-04
(0.00 - 6.00)
Determined by A1-02
216
when A1-02 ≠ 5
20.0 when A1-02 = 5
(0.0 - 1000.0 ms)
1.05
216
(1.00 - 1.20)

Advertisement

Table of Contents
loading