O2: Keypad Operation - YASKAWA GA800 Programming Manual

Ac drive for industrial applications
Table of Contents

Advertisement

1.13 o: Keypad-Related Settings
No.
Name
(Hex.)
o1-56
Analog Gauge Area
Setting
(11EF)
RUN
o1-58
Motor Power Unit
Selection
(3125)

o2: Keypad Operation

No.
Name
(Hex.)
o2-01
LO/RE Key Function
Selection
(0505)
o2-02
STOP Key Function
Selection
(0506)
o2-03
User Parameter Default
Value
(0507)
o2-04
Drive Model (KVA)
Selection
(0508)
o2-05
Home Mode Freq Ref
Entry Mode
(0509)
o2-06
Keypad Disconnect
Detection
(050A)
o2-07
Keypad RUN Direction
@ Power-up
(0527)
o2-09
Reserved
(050D)
o2-23
External 24V Powerloss
Detection
(11F8)
RUN
o2-24
LED Light Function
Selection
(11FE)
102
V/f
CL-V/f
OLV
CLV
AOLV
Sets the value used to display the monitor set in o1-24 [Custom Monitor 1] as an analog
meter. This parameter is only available when using an LCD keypad.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the setting unit for parameters that set the motor rated power.
0 : kW
1 : HP
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that lets you use
Modes.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to stop the drive with the
command source for the drive is REMOTE (external) and not assigned to the keypad.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to keep the settings of changed parameters as user parameter defaults to
use during initialization.
0 : No change
1 : Set defaults
2 : Clear all
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Drive Model code. Set this parameter after replacing the control board.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that makes it necessary to push the
reference value with the keypad when in Drive Mode.
0 : ENTER Key Required
1 : Immediate / MOP-style
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that stops the drive if you disconnect the keypad connection cable from
the drive or if you damage the cable while the keypad is the Run command source.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the direction of motor rotation when the drive is energized and the keypad is the Run
command source.
0 : Forward
1 : Reverse
-
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to give a warning when the backup external 24 V power supply turns off
when the main circuit power supply is in operation.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to show the LED status rings and keypad LED lamps.
Note:
When you use A1-03 [Initialize Parameters] to initialize the drive, the drive will not
reset this parameter.
0 : Enable Status Ring & Keypad LED
1 : LED Status Ring Disable
2 : Keypad LED Light Disable
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
to switch between LOCAL and REMOTE
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
button on the keypad when the Run
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
to change the frequency
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
Ref.
(Range)
100.0%
517
(0.0 - 100.0%)
1
517
(0, 1)
Default
Ref.
(Range)
1
517
(0, 1)
1
518
(0, 1)
0
518
(0 - 2)
Determined by the drive
519
(-)
0
520
(0, 1)
1
520
(0, 1)
0
520
(0, 1)
-
520
0
521
(0, 1)
2
521
(0 - 2)

Advertisement

Table of Contents
loading

Table of Contents