L6: Torque Detection - YASKAWA GA800 Programming Manual

Ac drive for industrial applications
Table of Contents

Advertisement

L6: Torque Detection

No.
Name
(Hex.)
L6-01
Torque Detection
Selection 1
(04A1)
L6-02
Torque Detection Level 1
(04A2)
L6-03
Torque Detection Time 1
(04A3)
L6-04
Torque Detection
Selection 2
(04A4)
L6-05
Torque Detection Level 2
(04A5)
L6-06
Torque Detection Time 2
(04A6)
L6-07
Torque Detection Filter
Time
(04E5)
L6-08
Mechanical Fatigue
Detect Select
(0468)
L6-09
Mech Fatigue Detect
Speed Level
(0469)
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed range that detects overtorque and undertorque and the operation of drives
(operation status) after detection.
0 : Disabled
1 : oL @ Speed Agree - Alarm only
2 : oL @ RUN - Alarm only
3 : oL @ Speed Agree - Fault
4 : oL @ RUN - Fault
5 : UL @ Speed Agree - Alarm only
6 : UL @ RUN - Alarm only
7 : UL @ Speed Agree - Fault
8 : UL @ RUN - Fault
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, drive rated
output current = 100% value. In vector control, motor rated torque = 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection time for Overtorque/Undertorque Detection 1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed range that detects overtorque and undertorque and the operation of drives
(operation status) after detection.
0 : Disabled
1 : oL @ Speed Agree - Alarm only
2 : oL @ RUN - Alarm only
3 : oL @ Speed Agree - Fault
4 : oL @ RUN - Fault
5 : UL @ Speed Agree - Alarm only
6 : UL @ RUN - Alarm only
7 : UL @ Speed Agree - Fault
8 : UL @ RUN - Fault
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for Overtorque/Undertorque Detection 2. In V/f control, drive rated
output current = 100% value. In vector control, motor rated torque = 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection time for Overtorque/Undertorque Detection 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant for a primary filter to the torque reference or to the output current
used to detect overtorque/undertorque.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed where the drive detects mechanical deterioration and how the drive operates
(operation status) after detection.
0 : Disabled
1 : oL5 @ Speed > L6-09 - Alarm
2 : oL5 @ lSpeedl > L6-09 - Alarm
3 : oL5 @ Speed > L6-09 - Fault
4 : oL5 @ lSpeedl > L6-09 - Fault
5 : UL5 @ Speed < L6-09 - Alarm
6 : UL5 @ lSpeedl < L6-09 - Alarm
7 : UL5 @ Speed < L6-09 - Fault
8 : UL5 @ lSpeedl < L6-09 - Fault
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed level where the drive will operate the mechanical deterioration detection
function, as a percentage of the Maximum Output Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
1.11 L: Protection Functions
Default
Ref.
(Range)
0
468
(0 - 8)
150%
469
(0 - 300%)
0.1 s
469
(0.0 - 10.0 s)
0
469
(0 - 8)
150%
470
(0 - 300%)
0.1 s
470
(0.0 - 10.0 s)
0 ms
470
(0 - 1000 ms)
0
470
(0 - 8)
110.0%
471
(-110.0 - 110.0%)
1
87