1.5 b: Application
No.
Name
(Hex.)
b5-65
PID Differential FB
Monitor Bias
(119F)
b5-66
PID Feedback Monitor
Level
(11DE)
b5-67
PID Differential FB
Monitor Lvl
(11DF)
b5-89
Sleep Method Selection
(0B89)
RUN
b5-90
EZ Sleep Unit
(0B90)
b5-91
EZ Sleep Minimum
Speed
(0B91)
RUN
EZ Sleep Level
b5-92
(0B92)
RUN
b5-93
EZ Sleep Time
(0B93)
RUN
b5-94
EZ Sleep Wake-up Level
(0B94)
RUN
b5-95
EZ Sleep Wake-up Mode
(0B95)
b5-96
EZ Sleep Wake-up Time
(0B96)
RUN

b6: Dwell Function

No.
Name
(Hex.)
b6-01
Dwell Reference at Start
(01B6)
b6-02
Dwell Time at Start
(01B7)
b6-03
Dwell Reference at Stop
(01B8)
b6-04
Dwell Time at Stop
(01B9)
30
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the signal level for the monitor specified in b5-55 [PID Feedback Monitor Selection].
0 : Absolute
1 : Bi-directional (+/-)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the signal level for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
0 : Absolute
1 : Bi-directional (+/-)
V/f
CL-V/f
OLV
CLV
AOLV
Sets sleep and wake up operation when using PID.
0 : Standard
1 : EZ Sleep/Wake-up
V/f
CL-V/f
OLV
CLV
AOLV
Sets the measurement units for b5-91 [EZ Sleep Minimum Speed] and b5-92 [EZ Sleep
Level].
0 : 0.1Hz units
1 : rev/min
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum speed for the EZ Sleep/Wakeup function. This parameter uses the
largest value from b5-91, b5-34 [PID Output Lower Limit Level], and d2-02 [Frequency
Reference Lower Limit].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the value that the output frequency or motor speed must be less than for longer than
b5-93 [EZ Sleep Time] to enter Sleep Mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the output frequency or motor speed must be less than b5-92
[EZ Sleep Level] to enter Sleep Mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level at which the drive resumes operation when exiting Sleep Mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the wake-up mode to use when exiting Sleep Mode.
0 : Absolute
1 : Setpoint Delta
V/f
CL-V/f
OLV
CLV
AOLV
Sets the EZ Wake-up time.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output frequency that the drive will hold momentarily when the motor starts.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the drive will hold the output frequency when the motor starts.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output frequency that the drive will hold momentarily when ramping to stop the
motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time for the drive to hold the output frequency when ramping to stop the
motor.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
Ref.
(Range)
0.00
236
(-10.00 - +10.00)
0
236
(0, 1)
0
236
(0, 1)
0
236
(0, 1)
0
237
(0, 1)
0.0 Hz or 0 min
-1
(r/min)
237
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
0.0 Hz or 0 min
-1
(r/min)
237
(0.0 to 590.0 Hz or 0 to
-1
35400 min
(r/min))
5.0 s
237
(0.0 - 1000.0 s)
0.00%
237
(0.00 - 600.00%)
0
238
(0, 1)
1.0 s
238
(0.0 - 1000.0 s)
Default
Ref.
(Range)
0.0
238
(Determined by A1-02)
0.0 s
239
(0.0 - 10.0 s)
0.0
239
(Determined by A1-02)
0.0 s
239
(0.0 - 10.0 s)

Advertisement