U: Monitors; U1: Operation Status Monitors - YASKAWA GA800 Programming Manual

Ac drive for industrial applications
Table of Contents

Advertisement

1.17 U: Monitors

1.17

U: Monitors

U1: Operation Status Monitors

No.
Name
(Hex.)
U1-01
Frequency reference
(0040)
U1-02
Output Frequency
(0041)
U1-03
Output Current
(0042)
U1-04
Control Method
(0043)
U1-05
Motor Speed
(0044)
U1-06
Output Voltage Ref
(0045)
U1-07
DC Bus Voltage
(0046)
U1-08
Output Power
(0047)
U1-09
Torque Reference
(0048)
112
V/f
CL-V/f
OLV
CLV
AOLV
Shows the actual frequency reference value. Parameter o1-03 [Keypad Display Unit Selection] sets
the display units.
Unit: 0.01 Hz
V/f
CL-V/f
OLV
CLV
AOLV
Shows the actual output frequency. Parameter o1-03 [Keypad Display Unit Selection] sets the display
units.
Unit: 0.01 Hz
V/f
CL-V/f
OLV
CLV
AOLV
Shows the actual output current.
The keypad shows the value of U1-03 in amperes (A). When looking at the monitor through
MEMOBUS/Modbus communications, the current is "8192 = drive rated current (A)." Calculate the
current from the monitor value that is in at MEMOBUS/Modbus communications using "Numerals
being displayed / 8192 × drive rated current (A)."
Unit: Determined by the drive model.
• 0.01 A: 2004 to 2042, 4002 to 4023
• 0.1 A: 2056 to 2415, 4031 to 4720
V/f
CL-V/f
OLV
CLV
AOLV
Shows the drive control method.
0 : V/f Control
1 : V/f Control with Encoder
2 : Open Loop Vector
3 : Closed Loop Vector
4 : Advanced Open Loop Vector
5 : PM Open Loop Vector
6 : PM Advanced Open Loop Vector
7 : PM Closed Loop Vector
8 : EZ Vector Control
V/f
CL-V/f
OLV
CLV
AOLV
Shows the actual detected motor speed. Parameter o1-03 [Keypad Display Unit Selection] sets the
display units.
Unit: 0.01 Hz
V/f
CL-V/f
OLV
CLV
AOLV
Shows the output voltage reference.
Unit: 0.1 V
V/f
CL-V/f
OLV
CLV
AOLV
Shows the DC bus voltage.
Unit: 1 V
V/f
CL-V/f
OLV
CLV
AOLV
Shows the internally-calculated output power.
Changing the setting of A1-02 [Control Method Selection] also changes the signal level of the analog
output.
• A1-02 = 0, 1: Drive capacity (kW)
• A1-02 = 2, 3, 4: Motor Rated Power [E2-11] (kW)
• A1-02 = 5, 6, 7: PM Motor Rated Power [E5-02] (kW)
• A1-02 = 8: Motor Rated Power [E9-07] (kW)
Unit: The display units are different for different models:
• 0.01 kW: 2004 to 2042, 4002 to 4023
• 0.1 kW: 2056 to 2415, 4031 to 4720
V/f
CL-V/f
OLV
CLV
AOLV
Shows the internal torque reference value.
Unit: 0.1%
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
MFAO Signal Level
10 V = Maximum frequency
(-10 V to +10 V)
10 V = Maximum frequency
(-10 V to +10 V)
10 V = Drive rated current
No signal output available
10 V = Maximum frequency
(-10 V to +10 V)
200 V class: 10 V = 200
Vrms
400 V class: 10 V = 400
Vrms
200 V class: 10 V = 400 V
400 V class: 10 V = 800 V
10 V: Drive capacity (motor
rated power) kW
(-10 V to +10 V)
10 V = Motor rated torque
(-10 V to +10 V)