L3: Stall Prevention - YASKAWA GA800 Programming Manual

Ac drive for industrial applications
Table of Contents

Advertisement

No.
Name
(Hex.)
L2-30
KEB Zero Speed
Operation
(045E)
Expert
L2-31
KEB Start Voltage Offset
Level
(045D)
Expert

L3: Stall Prevention

No.
Name
(Hex.)
L3-01
Stall Prevention during
Accel
(048F)
L3-02
Stall Prevent Level during
Accel
(0490)
L3-03
Stall Prevent Limit during
Accel
(0491)
L3-04
Stall Prevention during
Decel
(0492)
L3-05
Stall Prevention during
RUN
(0493)
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the operation when the output frequency decreases below the zero level (DC braking
injection starting frequency) during KEB deceleration when L2-01 = 3 to 5 [Power Loss
Ride Through Select = Kinetic Energy Backup: L2-02, Kinetic Energy Backup: CPU
Power, or Kinetic Energy Backup: DecelStop].
0 : Baseblock
1 : DC Injection Braking
V/f
CL-V/f
OLV
CLV
AOLV
Sets the KEB start voltage offset.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the method of the Stall Prevention During Acceleration.
0 : Disabled
1 : Enabled
2 : Intelligent (Ignore Decel Ramp)
3 : Current Limit Acceleration
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output current level to activate the Stall Prevention function during acceleration as
a percentage of the drive rated output current.
Note:
The upper limit of the setting range changes when C6-01 [Normal / Heavy Duty
Selection] changes.
• 150% when C6-01 = 0 [Heavy Duty Rating].
• 110% when C6-01 = 1 [Normal Duty Rating].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the lower limit for the stall prevention level used in the constant output range as a
percentage of the drive rated output current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the method that the drive will use to prevent overvoltage faults when decelerating.
Note:
1.
To connect a dynamic braking option (braking resistor or braking resistor unit) to
the drive, set this parameter to 0 or 3. Parameter values 1, 2, 4, and 5 will enable
Stall Prevention function during deceleration, and the dynamic braking option will
not function.
2.
The setting range changes when the A1-02 [Control Method Selection] value
changes:
• When A1-02 = 5 [OLV/PM], the setting range is 0 to 2.
• When A1-02 = 6, 7, 8 [AOLV/PM, CLV/PM, EZOLV], the setting range is 0, 1.
0 : No
1 : General Purpose
2 : Intelligent (Ignore Decel Ramp)
3 : General Purpose w/ DB resistor
4 : Overexcitation/High Flux
5 : Overexcitation/High Flux 2
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to enable and disable Stall Prevention During Run.
Note:
1.
An output frequency lower than 6 Hz will disable Stall Prevention during Run.
The L3-05 and L3-06 [Stall Prevent Level during Run] settings do not have an
effect.
2.
The setting range changes when the A1-02 [Control Method] value changes:
• A1-02 = 0, 1, 5 [V/f, CL-V/f, OLV/PM]: 0 to 2
• A1-02 =8[EZOLV]: 0, 3
0 : Disabled
1 : Deceleration Time 1 (C1-02)
2 : Deceleration Time 2 (C1-04)
3 : Intelligent (Ignore Decel Ramp)
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
1.11 L: Protection Functions
Default
Ref.
(Range)
0
451
(0, 1)
Determined by A1-02
452
(200 V Class: 0 - 100
V,400 V Class: 0 - 200 V)
Default
Ref.
(Range)
1
452
(0 to 3)
Determined by C6-01 and
454
L8-38
(0 - 150%)
50%
454
(0 - 100%)
1
455
(Determined by A1-02)
2
456
(0 - Determined by A1-
02)
1
83

Advertisement

Table of Contents
loading

Table of Contents