F6: Communication Options - YASKAWA GA800 Programming Manual

Ac drive for industrial applications
Table of Contents

Advertisement

1.9 F: Options
No.
Name
(Hex.)
F5-08
Terminal M3-M4
Function Select
(03A0)
F5-09
DO-A3 Output Mode
Selection
(03A1)

F6: Communication Options

No.
Name
(Hex.)
F6-01
Communication Error
Selection
(03A2)
F6-02
Comm External Fault
(EF0) Detect
(03A3)
F6-03
Comm External Fault
(EF0) Select
(03A4)
F6-04
bUS Error Detection
Time
(03A5)
F6-06
Torque Reference/Limit
by Comm
(03A7)
F6-07
Multi-Step Ref @
NetRef/ComRef
(03A8)
F6-08
Comm Parameter Reset
@Initialize
(036A)
F6-10
CC-Link Node Address
(03B6)
54
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function of terminal M3-M4 on the DO-A3 option. Set F5-09 = 2 [DO-A3 Output
Mode Selection = Programmable (F5-01 to F5-08)] to enable this function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output mode of signals from the DO-A3 option.
0 : Predefined Individual Outputs
1 : Binary Output
2 : Programmable (F5-01 to F5-08)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the method to stop the motor or let the motor continue operating when the drive
detects a bUS [Option Communication Error].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop
3 : Alarm Only
4 : Alarm (Run at d1-04)
5 : Alarm - Ramp Stop
V/f
CL-V/f
OLV
CLV
AOLV
Sets the conditions at which EF0 [Option Card External Fault] is detected.
0 : Always Detected
1 : Detected during RUN Only
V/f
CL-V/f
OLV
CLV
AOLV
Sets the method to stop the motor or let the motor continue operating when the drive
detects an EF0 [Option Card External Fault].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
V/f
CL-V/f
OLV
CLV
AOLV
Sets the delay time for the drive to detect bUS [Option Communication Error].
Note:
When you install an option card in the drive, the parameter value changes to 0.0 s.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that enables and disables the torque reference and torque limit received
from the communication option.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that enables and disables the multi-step speed reference when the
freqency reference source is NetRef or ComRef (communication option card or
MEMOBUS/Modbus communications).
0 : Disable Multi-Step References
1 : Enable Multi-Step References
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to initialize F6-xx and F7-xx parameters when the drive is initialized
with A1-03 [Initialize Parameters].
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
V/f
CL-V/f
OLV
CLV
AOLV
Sets the node address for CC-Link communication. Restart the drive after you change the
parameter setting.
Note:
Be sure to set a node address that is different than all other node addresses. Do not set
this parameter to 0. Incorrect parameter settings will cause AEr [Station Address
Setting Error] errors and the L.ERR LED on the option will come on.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
Ref.
(Range)
F
334
(0 - 1A7)
0
334
(0 - 2)
Default
Ref.
(Range)
1
340
(0 - 5)
0
341
(0, 1)
1
341
(0 - 3)
2.0 s
341
(0.0 - 5.0 s)
0
341
(0, 1)
0
342
(0, 1)
0
342
(0, 1)
0
342
(0 - 64)

Advertisement

Table of Contents
loading

Table of Contents