5. PARAMETERS
No./symbol/
Setting
name
digit
PN34
Set the 4th octet of the IP address of the network device allowed to be connected in
decimal.
*IPOA4
When [Pr. PN31] to [Pr. PN34] are all set to "0", the operation specification IP
Operation
address function is disabled.
specification
IP address 4
This parameter cannot be used when Modbus RTU is set.
When this function is enabled with CC-Link IE Field Network Basic communication,
the servo amplifier allows the following data 1) to 3) to be imported only if the IP
address of the master station (external device) matches with the operation
specification IP address. If they are mismatched, the data is discarded.
1) SDO Download (command: 4020h, sub command: 0002h)
2) SDO Object SubID Block Download (command: 4020h, sub command: 0006h)
3) CC-Link IE Field Network Basic request message (RWwn)
When this function is enabled with Modbus/TCP communication, the servo amplifier
allows the following data 4) to be imported only if the IP address of the client
(external device) matches with the operation specification IP address. If they are
mismatched, the data is discarded.
4) Modbus/TCP function code 10h
Monitoring, parameter setting, and test operation can be executed via Ethernet when
the IP addresses of a personal computer (MR Configurator2) and GOT are within the
range of the operation specification IP address. When they are out of the range,
communication to the servo amplifier cannot be established.
Setting range: 0 to 255
PN35
Set a value for the 3rd octet range of the IP address of the network device allowed to
be connected.
*IPOR3
The range for the IP address of the network device allowed to be connected is
Operation
between [Pr. PN33] and [Pr. PN35]. Set a value in decimal.
specification
IP address 3
Setting "256" disables the function.
range
This parameter cannot be used when Modbus RTU is set.
specification
Setting range: 0 to 256
PN36
Set a value for the 4th octet range of the IP address of the network device allowed to
be connected.
*IPOA4
The range for the IP address of the network device allowed to be connected is
Operation
between [Pr. PN34] and [Pr. PN36]. Set a value in decimal.
specification
IP address 4
Setting "256" disables the function.
range
This parameter cannot be used when Modbus RTU is set.
specification
Setting range: 0 to 256
Function
5 - 13
Initial
value
[unit]
0
256
256