3. Modbus/TCP
(2) Usage example
The following shows a setting example for writing "0100h" in the Modbus register 2102h ([Pr. PC02]).
Index
Name
2102h
PC02
Query Message
Transaction
Protocol
Length Field
Identifier
Identifier
16 bits
0000h
Set the following values to each Query Message.
Message field
Transaction Identifier
Protocol Identifier
Length Field
Unit Identifier
Function
Starting Address
No. of Registers
Byte Count
Data
Response Message
Transaction
Protocol
Length Field
Identifier
Identifier
2 × 8 bits
0000h
The following shows the information in each Response Message.
Message field
Transaction Identifier
Protocol Identifier
Length Field
Unit Identifier
Function
Starting Address
No. of Registers
Data type
U32
Unit
Function
Identifier
000Ah
FFh
10h
Set any value.
Set "0000h".
Set the byte length from Unit Identifier to Data.
Set "FFh".
Set "10h".
Set "2102h", the start address of the registers to which data is written.
Set "02h", because the total number of write points of the Modbus register 2102h is 2.
Set "04h". This means that data of 4 frames is sent.
Set values in order starting from the start address.
Lower-bit value of the register 2102h: "0100h"
Higher-bit value of the register 2102h: "0000h"
Unit
Function
Identifier
0006h
FFh
10h
Size
16 bits
Transaction Identifier received from the client (controller) is copied and returned.
16 bits
The value "0000h" is returned.
16 bits
The byte length from Unit Identifier to Data is returned.
8 bits
Unit Identifier received from the client (controller) is copied and returned.
8 bits
When the message was received without errors, "10h" is returned.
16 bits
The value "2102h", the start address of the holding registers to which the data
was written is returned.
H: "21h"
L: "02h"
16 bits
The number of registers to write "02h" is returned.
No. of
Access
Registers
rw
2
Starting
No. of
Address
Registers
H
L
H
L
21h
02h
00h
02h
Description
Starting Address
H
L
H
21h
02h
00h
Description
3 - 9
Continuous
Setting value
read/write
00000100h
Data
Byte
Count
H
L
H
04h
01h
00h
00h
No. of Points
L
02h
L
00h