5. PARAMETERS
No./symbol/
Setting
name
digit
PN32
Set the 2nd octet of the IP address of the network device allowed to be connected in
decimal.
*IPOA2
When [Pr. PN31] to [Pr. PN34] are all set to "0", the operation specification IP
Operation
address function is disabled.
specification
IP address 2
This parameter cannot be used when Modbus RTU is set.
When this function is enabled with CC-Link IE Field Network Basic communication,
the servo amplifier allows the following data 1) to 3) to be imported only if the IP
address of the master station (external device) matches with the operation
specification IP address. If they are mismatched, the data is discarded.
1) SDO Download (command: 4020h, sub command: 0002h)
2) SDO Object SubID Block Download (command: 4020h, sub command: 0006h)
3) CC-Link IE Field Network Basic request message (RWwn)
When this function is enabled with Modbus/TCP communication, the servo amplifier
allows the following data 4) to be imported only if the IP address of the client
(external device) matches with the operation specification IP address. If they are
mismatched, the data is discarded.
4) Modbus/TCP function code 10h
Monitoring, parameter setting, and test operation can be executed via Ethernet when
the IP addresses of a personal computer (MR Configurator2) and GOT are within the
range of the operation specification IP address. When they are out of the range,
communication to the servo amplifier cannot be established.
Setting range: 0 to 255
PN33
Set the 3rd octet of the IP address of the network device allowed to be connected in
decimal.
*IPOA3
When [Pr. PN31] to [Pr. PN34] are all set to "0", the operation specification IP
Operation
address function is disabled.
specification
IP address 3
This parameter cannot be used when Modbus RTU is set.
When this function is enabled with CC-Link IE Field Network Basic communication,
the servo amplifier allows the following data 1) to 3) to be imported only if the IP
address of the master station (external device) matches with the operation
specification IP address. If they are mismatched, the data is discarded.
1) SDO Download (command: 4020h, sub command: 0002h)
2) SDO Object SubID Block Download (command: 4020h, sub command: 0006h)
3) CC-Link IE Field Network Basic request message (RWwn)
When this function is enabled with Modbus/TCP communication, the servo amplifier
allows the following data 4) to be imported only if the IP address of the client
(external device) matches with the operation specification IP address. If they are
mismatched, the data is discarded.
4) Modbus/TCP function code 10h
Monitoring, parameter setting, and test operation can be executed via Ethernet when
the IP addresses of a personal computer (MR Configurator2) and GOT are within the
range of the operation specification IP address. When they are out of the range,
communication to the servo amplifier cannot be established.
Setting range: 0 to 255
Function
5 - 12
Initial
value
[unit]
0
0