Electrical Requirements
Ground and Terminal Block Locations for CE Models
1. Earth/Ground
2. Junction Box
3. Terminal Block
4. Power Disconnect (Models Through 7/31/11)
5. Electrical Service
To Connect Electrical Service To The
Tumble Dryer
NOTE: The wiring diagram is located in the junction
box.
1. Install a circuit breaker as close to the tumble dryer as possi-
ble. If more than one tumble dryer is being installed, a discon-
nect switch or circuit breaker should be provided for each.
This will make it possible to disconnect each tumble dryer for
maintenance purposes.
2. Connect the conduit-encased leads to the disconnect switch,
or circuit breaker. Connect the wire leads to the appropriate
labeled terminal on the terminal block. The ground wire must
be connected to the ground connection as shown in Figure 26
or Figure 27 .
3. Check the electrical service phase sequence (three phase only)
as follows:
a. Energize the electrical service (on reversing tumble dry-
ers, ensure nonreversing is selected) and momentarily start
the tumble dryer. Check the direction of the cylinder rota-
tion. If the cylinder rotates clockwise (viewed from the
front), the phase sequence is correct. If the cylinder rotates
counterclockwise, proceed with step b.
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
5
4
3
Figure 27
1
2
TMB2247N_SVG
NOTE: When viewed from the front, the fan
should rotate clockwise on 050 and 075 series
models and counterclockwise on F75 series
models.
b. Disconnect and reverse any two service leads on the ter-
minal block (example: switch L2 and L3 on terminal
block).

Jumper Configuration Instructions

Changing the transformer configuration jumper is required, PRI-
OR TO SUPPLYING POWER TO THE MACHINE, if any of
the following apply:
IMPORTANT: Failure to install the proper configuration
jumper may result in damage to sensitive electronic
controls and may void warranty.
Location voltage 200 – 208 Volt service and connecting a
model rated for 240 Volt operation.
Replace the 240 Volt jumper with the 208 Volt jumper per the
conversion label, located on the rear of the tumble dryer, sign and
date conversion label to document the conversion.