Operation; Inspection And Preparation Before Operation; Operation Method; Test Operation - IMO VXSM75-1 Instruction Manual

Imo jaguar vxsm general purpose inverter
Table of Contents

Advertisement

3. Operation

3-1
Inspection and Preparation
Before Operation
Check the following before starting operation.
(1) Check if connection is correct.
Especially check if the power cables are
connected to inverter output terminals U, V
and W and that the grounding cable is
grounded without fail.
(2) Check for short circuits between terminals
and exposed live parts and ground faults.
(3) Check for loose terminals, connectors and
screws.
(4) Check if the motor is separated from
mechanical equipment.
(5) Turn the switches off so that the inverter
does not start or operate erroneously at
power-on.
(6) After the power is turned on, check the
following.
a. Check if the keypad panel shows an alarm.
b. Check if the fan built in the inverter rotates.
(1.5 kW or above)
WARNING
• Be sure to install the terminal cover
before turning the power on.
• Do not remove the cover during power
application.
• Do not operate switches with wet hands.
Otherwise electric shock could occur.
3-2

Operation Method

There are various operation methods. Refer to
chapter 4 "Keypad Panel" and chapter 5
"Selecting Functions" to select the method most
suitable for the purpose and operation
specification. Table 3-2-1 shows general
operation methods.
3-3

Test Operation

After checking for errors in section 3-1, perform
a test operation.
In the factory shipment state, the inverter is in
the keypad panel operation mode.
(1) Turn the power on and check that the LED
blinks while indicating the 0.00 Hz
frequency.
(2) Using the
key, set the frequency to a low
V
frequency such as 5 Hz.
(3) To turn forward: F02 = 2
To reverse: F02 = 3
After setting the above, press the
operation. To stop, press the
Operation
Fig. 3-1-1 Inverter connection diagram
(4) Check the following points.
(5) Referring to function code P04 Motor 1
Caution 1: If any abnormality is found to the
inverter or motor, immediately stop operation
and determine the cause referring to chapter 7
Troubleshooting.
Caution 2: If voltage is applied to the L1/R, L2/S
and L3/T or L1/L and L2/N main circuit power
supply terminals even after the inverter stops,
the inverter output terminals U, V and W are live
and you will receive electric shock when
touching the terminals. As well, the smoothing
capacitor is not discharged immediately after
the power is turned off and it takes time for the
capacitor to be discharged.
To touch the electric circuit after turning the
power off, check that the charge lamp is unlit
and check for safe voltage using a multimeter.
key to start
Table 3-2-1 General operation methods
RUN
key.
STOP
a. Check if the direction of rotation is correct.
b. Check for smooth rotation without motor
humming or excessive vibration.
c. Check for smooth acceleration and
deceleration.
(auto tuning), tune the motor constant.
When no abnormality is found, raise the
operation frequency to check.
After checking for correct operation during the
above test operation, start normal operation.
Operation
Frequency
method
setting
Operation
Keypad
using keypad
panel keys
panel
,
,
Operation
Potentiometer
using external
or analog voltage P24, terminals
signal terminal
current or
multistep speed
operation
Operation
command
keypad panel
keys
V
RUN
STOP
,
Contact input
V
(switch),
terminals FWD-
REV-P24
3-1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents