Access Control Options - Inner Range CONCEPT IQ. PLUS Programmer's Manual

Table of Contents

Advertisement

CONCEPT IQ. PLUS Programmer's Manual.
ACCESS CONTROL
Access Review to General Review Option.
Setting General options to allow Access Review to be written to General Review
1) Enable Option 3, in General Options 4.
This option should be enabled with caution because of the limited size of the buffer, Access events
could force General events out of the buffer before they can be reviewed.
Default setting is disabled, requiring the Upload/Download software addon to view the Access Review.
Door Forced to trigger Siren.
The Door Forced system input can be set to enable the Siren output when there is a Door Forced alarm.
1) Enable Option 8, in System Input Siren Enable.
Door Forced to Report via Dialler.
The Door Forced system input can be set to enable reporting to the dialler.
1) Enable Option 1, in General options 4.
Door Open Too Long Report via Dialler.
The DOTL system input can be set to enable reporting to the dialler.
1) Enable Option 2, in General options 4.