Eclipse 8/ 32 Series - Installation Manual

2.6. Connection of Siren to PGM5 Output

In ECLIPSE 8 Alarm panel the PGM 5 (SIREN) output has a programmable active level. The default configuration of
PGM5 is with SIREN functionality. The output is activated in case of alarm event in the system. The output is non-
monitored.
In ECLIPSE 32 Alarm panel the PGM 5 (SIREN) output has a programmable active level. The default configuration of
PGM5 is with SIREN functionality. The output is activated in case of alarm event in the system. The output is monitored
and for correct functionality you should terminate the PGM 5 output with 1K resistance.
The internal structure is identical to the one shown in Figure 16 a) and we should point out that the transmitter can
pass through to GND electricity of up to 1 A.
Figure 19 shows how to connect SR110, SR120, SR200 and SR300 sirens using the SIREN output to ECLIPSE 8.
A) Connecting SR110 using a double-wire connection
C) Connecting SR120/SR200 using triple-wire
connection
Figure 19. Double- and triple-wire connection of sirens to ECLIPSE 8.
ATTENTION: The connections to ECLIPSE 32 are all the same with those shown on Figure 19 but you have to
terminate the PGM 5 output with 1K resistance (connect the resistance between PGM 5 and +AUX terminals on the
control panel or between +12V and BLA terminals of the siren), because the PGM 5 in ECLIPSE 32 is monitored –
Figure 20.
The BLOCK jumper in
SR120 (BL in SR200)
must be removed.
Figure 20. Triple-wire connection of SR300 to ECLIPSE 32.
B) Connecting SR120/SR200 using a double-wire connection
D) Connecting SR300 using triple-wire connection
22
The BLOCK jumper in SR120
(BL in SR200) must be set on.
The jumper BlockA -/+ determines
the level of the block signal:
set jumper - high level (12V)
removed jumper - low level (GND)