Installation and Programming Manual - СА62 Alarm Control Panel
2.8

Using of PGM1, PGM2 and PGM3 Programmable outputs

The СА62 Alarm panel PGM1, PGM2 and PGM3 outputs have a programmable active level. This allows them to be used
to transmit control signals towards external devices (e.g. a block siren input) or to directly control low-powered external
devices (e.g. relays, LED, etc.).
The internal structure of all PGMs is the same and is shown on Figure 12 a).
Figure 12 b) shows the connection of the relay and a light-emitting diode to the PGM. The active level of this connection
is low.
PGMx terminal
Permissible current:
- from +12 V - up to 10 mA
- towards GND - up to 100 mA
For SIREN output the
current supplied to GND
is up to 1 A.
Figure12. а) Internal structure of
programmable PGMx output
2.9 Using SIReN Programmable output (PGM4)
The СА62 Alarm panel SIREN output has a programmable active level. With the default configuration the output is
with SIREN and POLARITY set attributes, which can be programmed at ADDRESS 3041. The output is activated in
case of alarm event in the system.
The internal structure is identical to the one shown in Figure 12 a) and we should point out that the transmitter can pass
through to GND electricity of up to 1 A.
Figure 7 shows how to connect SR110E, SR120 and SR200 sirens using the SIREN output.
a) Connecting SR110E using
a double-wire
Figure12. b) Controlling light-emitting diode and
c) Connecting SR120/SR200 using triple-wire.
Figure 13. 7 Controlling sirens using SIREN output.
relay using PGM1 and PGM2 outputs
b) Connecting SR120/SR200
using a double-wire
the BLoCK jumper
in SR120 (BL in SR200)
must be removed.
the BLoCK jumper
in SR120 (BL in SR200)
must be set on.