Connecting Shutter Detector To A Zone (For Eclipse 32); Checking The Line Resistance - Teletek electronics ECLIPSE 8 Installation Manual

Alarm control panel
Hide thumbs Also See for ECLIPSE 8:
Table of Contents

Advertisement

2.3.2 Connecting shutter detector to a zone (for ECLIPSE 32)

The hardware implementation of Zone with set attribute "Pulse count" permits performance in pulse count mode,
suitable for connecting a rolling shutters detector. This mode counts short pulses - 2 to 4 ms for a period of 20
seconds. The first pulse starts a 20-second countdown during which pulses are expected to be received. Their number
is assigned at Address 2003 of the engineer programming. An alarm signal is emitted when this number is reached
within the time of 20 seconds. Otherwise, the pulse counter will be zeroed after the time of 20 seconds expires.
Activating the pulse count mode will automatically start when a number other than 0 is keyed in at Address 2003 of
the engineer programming.

2.3.3 Checking the line resistance

The engineer can check the line resistance of the zone after the initial power up of the system. It is suitable to perform
diagnostics of the zone troubles. The line resistance can be checked at address 2xx9, where "xx" in the zone number.
The address is accessible only through LCD type keyboard.
NOTE: The double zone connection is available only in ECLIPSE 32 control panel!
The displayed value can vary according the used hardware connection style in the system and has the following
meaning:
Connection style
Figure 9. Connecting of rolling shutter detector
Displayed value
< 1.5 kΩ
1
> 1.5 kΩ
< 0.75 kΩ
0.75 – 1.5 kΩ
2
> 1.5 kΩ
< 0.75 kΩ
0.75 – 1.5 kΩ
3
> 1.5 kΩ
< 0.75 kΩ
0.75 – 5.6 kΩ
4
> 5.6 kΩ
< 0.75 kΩ
0.75 – 1.5 kΩ
5
1.5 - 5.6 kΩ
> 5.6 kΩ
< 0.5 kΩ
0.5 – 1.5 kΩ
6
1.5 – 2.7 kΩ
2.7 kΩ - ∞
< 0.5 kΩ
0.5 – 1.5 kΩ
1.5 – 2.7 kΩ
7
2.7 – 4.9 kΩ
> 4.9 kΩ
< 0.75 kΩ
0.75 – 1.5 kΩ
1.5 – 2.5 kΩ
8
2.5 – 3.7 kΩ
3.7 – 4.9 kΩ
> 4.9 kΩ
< 0.5 kΩ
0.5 - 0.75 kΩ
0.75 - 1.5 kΩ
9
1.5 – 2.7 kΩ
> 2.7 kΩ
Description
The zone is closed.
The zone is open.
The zone is open.
The zone is closed.
The zone is open.
The zone is open.
The zone is closed.
The zone is open.
The zone is closed.
The zone is open.
Tamper break down.
Tamper short-circuit.
The zone is closed.
The zone is open.
Tamper break down.
The both zones are closed.
st
The 1
zone is open, the 2
st
The 1
zone is closed, the 2
The both zones are open.
The both zones are closed.
st
The 1
zone is open, the 2
st
The 1
zone is closed, the 2
The both zones are open.
Tamper break down.
Tamper short-circuit.
The both zones are closed.
st
The 1
zone is open, the 2
st
The 1
zone is closed, the 2
The both zones are open.
Tamper break down.
Tamper short-circuit.
The both zones are closed.
st
The 1
zone is closed, the 2
st
The 1
zone is open, the 2
The both zones are open.
13
Eclipse 8/ 32 Series - Installation Manual
nd
zone is closed.
nd
zone is open.
nd
zone is closed.
nd
zone is open.
nd
zone is closed.
nd
zone is open.
nd
zone is open.
nd
zone is closed.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eclipse 32Eclipse 16

Table of Contents