Control Panels Pcb Layouts; Eclipse 8 - Teletek electronics ECLIPSE 8 Installation Manual

Alarm control panel
Hide thumbs Also See for ECLIPSE 8:
Table of Contents

Advertisement

2.2. Control Panels PCB Layouts

2.2.1 ECLIPSE 8

ECLIPSE 8 - Terminals and components:
17VAC – Power supply from a mains transformer 17V / 17VA, fuse 0.63А
GND – Common ground
+/- AUX – Power supply for detectors with consumption up to 0.75А
+PGM – Power supply of auxiliary devices with consumption up to 0.75А
PGM 1-3 – Programmable outputs, 100mA, ОС type (open collector)
PGM 4 – Programmable output / Serial link, 100mA, ОС type (open collector)
PGM 5/SIREN – Programmable output, high power up to 1А, ОС type (open collector), for connecting siren
Z1-Z6 – Zone inputs
COM – Common ground
RED, GRN, YEL, BLK - System bus interface for connection of keyboards, proximity card readers, expanders, etc.
Jumper RESET – Jumper for total hardware reset of the control panel
Serial – PC Interface connection
VOICE - Interface connector for mounting of Voice module ECLIPSE VD
BATT – Terminals for connecting the back-up battery
PSTN terminals:
TIP1, RING1 – Connect the telephone
TIP, RING – Connect the PSTN line
GND – Common ground
Fuses, PTC type:
F1 – Fuse for the back-up battery: 0,75A
F2 – Fuse for PGM outputs: 0.5A
F3 – Fuse for AUX outputs: 0.5A
LED indication:
PSTN – LED for the status of the built-in digital communicator.
BUS LED – LED for the status of the system bus:
BUS LED
Lights on permanently
Red
RESET Jumper is set
Yellow
Short circuit of the system bus
Green
Selected device of the system bus
Figure 5. ECLIPSE 8 control panel
Wrong connection of the system bus
Normal operation mode
9
Eclipse 8/ 32 Series - Installation Manual
Blinks in pulses
Low power supply