Connection Of Siren To Power Pgm Output - Teletek electronics ECLIPSE 8 Installation Manual

Alarm control panel
Hide thumbs Also See for ECLIPSE 8:
Table of Contents

Advertisement

2.6. Connection of Siren to Power PGM Output

In ECLIPSE 8/16 Alarm panel, the PGM 5 (BELL) output has a programmable active level. The default configuration of
PGM5 is with SIREN functionality. The output is activated in case of alarm event in the system. The output is non-
monitored.
In ECLIPSE 32/99 Alarm panel, the PGM 5 (BELL) output has a programmable active level. The default configuration
of PGM5 is with SIREN functionality. The output is activated in case of alarm event in the system. The output is
monitored and for correct functionality you should terminate the PGM 5 output with 1K resistance.
The internal structure is identical to the one shown in Figure 20 a) and we should point out that the transmitter can
pass through to GND electricity of up to 1 A.
Figure 22 shows how to connect SR110, SR120, SR200, SR300 and SR400 sirens using the BELL output to ECLIPSE
8.
A) Connecting SR110 using a double-wire connection
C) Connecting SR120/SR200 using triple-wire
connection
Figure 22. Double- and triple-wire connection of sirens to ECLIPSE 8.
ATTENTION: The connections to ECLIPSE 32/99 are all the same with those shown on Figure 22 but you have to
terminate the PGM 5 output with 1K resistance (connect the resistance between PGM 5 and +AUX terminals on the
control panel or between +12V and BLA terminals of the siren), because the PGM 5 in ECLIPSE 32 and ECLIPSE 99
is a monitored output – Figure 23.
Figure 23. Example for triple-wire connection of SR300 to ECLIPSE 32.
The BLOCK jumper in
SR120 (BL in SR200)
must be removed.
Eclipse 8/16/32/99 Series - Installation Manual
B) Connecting SR120/SR200 using a double-wire connection
D) Connecting SR300/SR400 using triple-wire connection
29
The BLOCK jumper in SR120
(BL in SR200) must be set on.
The jumper BlockA -/+ determines
the level of the block signal:
set jumper - high level (12V)
removed jumper - low level (GND)