Mitsubishi GT16 User Manual page 95

Hide thumbs Also See for GT16:
Table of Contents

Advertisement

(6) Ethernet connection
• Strip the outer insulation layer at both ends of the cable by the length shown below to expose the braided
shield for grounding. (For grounding with cable clamps. (refer to Section 5.4.3.))
• Attach the ferrite core to the cable in the position as illustrated below.
(a) When connecting to the Ethernet interface
GOT side
120 or
less
(4.72)
230 or less
(9.06)
(b) When connecting to the multimedia unit (GT16M-MMR)
GOT side
120 or
less
230 or less
(9.06)
(7) External I/O device connection
• Strip the outer insulation layer at both ends of the cable by the length shown below to expose the braided
shield for grounding. (For grounding with cable clamps (Refer to Section 5.4.3.))
• Connect the braided shield to the connector with the connector cover.
• Twist power cables.
GOT side
Braided shield
Connector cover
360 or less
(14.17)
5.4 Precautions for Wiring/Connecting the EMC Directive-Compliant Product
Ferrite Core
(ZCAT3035-1330)
40
(1.57)
Ferrite Core
(ZCAT3035-1330)
40
(1.57)
Power cable
40
(1.57)
PLC/
personal computer side
120 or
less
(4.72)
40
400 or less
(15.75)
(1.57)
Personal computer side
120 or
less
External I/O device side
40
360 or less
(14.17)
(1.57)
Unit : mm (inch)
Unit : mm (inch)
Unit : mm (inch)
5 - 18
1
2
3
4
5
6
7
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Got 1000 gt16

Table of Contents