Factory Settings Of The Control Unit - Siemens SINAMICS CU240S DP-F Operating Instructions Manual

Hide thumbs Also See for SINAMICS CU240S DP-F:
Table of Contents

Advertisement

Description

3.5 Factory Settings of the Control Unit

3.5
Factory Settings of the Control Unit
Factory settings for command and setpoint source
P0700 = 0 is the same as P0700 = 2 or 6 dependent on type of Control Unit.
Note
Setting P0700 = 6 (command source via fieldbus communication) and P1000 = 6 (setpoint
source via fieldbus communication) are not possible with a CU240S.
Setting P0700 = 5 (command source via USS communication) and P1000 = 5 (setpoint
source via USS communication) are not possible with a CU240S DP or a CU240S DP-F.
Table 3-3
Functions of Digital Inputs and Digital Outputs with default settings of P0700
Function
ON/OFF1
Reverse
Fault acknowledge
Fixed freq. selector bit0
Fixed freq. selector bit1
Fixed freq. selector bit2
Fixed freq. selector bit3
Drive fault active
Drive warning active
Note
Digital inputs 7 and 8 and Digital output 2 are disabled per default.
26
CU240S (P0700 = 2)
Parameter
Source
P0701 = 1
DI0
P0702 = 12
DI1
P0703 = 9
DI2
P0704 = 15
DI3
P0705 = 16
DI4
P0706 = 17
DI5
P0707 = 18
DI6
P0731 = 52.3
DO0
P0732 = 52.7
DO1
CU240S DP (P0700 = 6)
CU240S PN (P0700 = 6)
Parameter
Source
r2090.00
CW1, Bit 0
r2090.11
CW1, Bit 11
r2090.07
CW1, Bit 7
r2091.00
CW2, Bit 0
r2091.01
CW2, Bit 1
r2091.02
CW2, Bit 2
r2091.03
CW2, Bit 3
P0731 = 52.3
DO0
P0732 = 52.7
DO1
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
CU240S DP-F (P0700 = 6)
CU240S PN-F (P0700 = 6)
Parameter
Source
r2090.00
CW1, Bit 0
r2090.11
CW1, Bit 11
r2090.07
CW1, Bit 7
r2091.00
CW2, Bit 0
r2091.01
CW2, Bit 1
r2091.02
CW2, Bit 2
---
---
P0731 = 52.3
DO0
P0732 = 52.7
DO1
Control Units CU240S