6.4 Communication via PROFIBUS
Information about the parameter request:
● Request_reference:
● Request_ID:
● Drive_object_ID:
● No_of_parameters:
● Attribute:
● No_of_elements:
● Parameter_number:
● Subindex:
● Format:
● No_of_values:
● Value:
For the acyclic communication in OB1 a write request must be send to the drive with
WR_REC (SFC 58)
Figure 6-13
162
The value is selected at random from the valid value range. The request reference
establishes the relationship between request and response.
0x02 --> This identifier is required for a write request.
0x00 -> Device-Representative (for G120 inverters = 0).
0x01 --> One parameter request.
0x10 -> The parameter value are to be written.
0x01 -> 1 array element is written.
043A -> Parameter P1082 (max. frequency); 043A hex = 1082 dec.
0x00 -> ID for the first array element.
0x43 -> Floating Point data type (refer to the Parameter List).
0x01 -> One value is written to the parameter in the specified format.
1.000000e+002 -> maximum frequency 100 Hz.
Acyclic communication in OB1
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD