Reset Parameters To Factory Settings - Siemens SINAMICS CU240S DP-F Operating Instructions Manual

Hide thumbs Also See for SINAMICS CU240S DP-F:
Table of Contents

Advertisement

5.5.5

Reset Parameters to Factory Settings

Overview
With a factory reset via P0970 the initial state of the all the inverter parameters can be re-
established.
The factory setting values are designated as "Factory setting" in the Parameter Manual.
For further information, refer to the section "Factory Settings of the Control Unit" in this
manual.
Note
When resetting the parameters to the factory setting, the communications memory is re-
initialized. This means that communications are interrupted for the time it takes to perform
the reset.
Parameter reset in case of CUs with fail-safe functions
Parameters that don't relate to fail-safe functions are reset with P0970 = 1.
To reset parameters that relate to fail-safe functions an additional parameter reset with
P0970 = 10 must be performed. This parameter reset is password protected.
In case of a parameter reset with P0970 = 10 an acceptance test necessary.
Reset to the factory setting
Parameter or action
P0003 = 1
P0004 = 0
P0010 = 30
P0970 = 1
BUSY (on BOP)
Progress bar (STARTER)
Note
The following parameters will not be changed with a factory reset:
• P0014 Store mode
• P0100 Europe / North America
• P0201 power stack code number
• P8458 clone control
• Communication parameters
• Data depending on actual Power Module
Control Units CU240S
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
WARNING
Description
User access level*
1: Standard: Allows access into most frequently used parameters.
Parameter filter
0: All parameters
Commissioning parameter*
30: Factory setting, parameter transfer
Factory reset*
1: Parameter reset to the default values
When the factory reset has been finished, P0970 and P0010 are set to 0 and the BOP
changes back to the standard display.
Commissioning
5.5 Commissioning using the BOP
77