Profisafe Telegram Structure - Siemens SINAMICS CU240S DP-F Operating Instructions Manual

Hide thumbs Also See for SINAMICS CU240S DP-F:
Table of Contents

Advertisement

6.2.3

PROFIsafe Telegram Structure

Description
The fail-safe functions can be triggered via the fail-safe digital inputs FDI0 and FDI1 or via
PROFIsafe signals (see P9603 and 9803).
To use PROFIsafe for triggering the fail-safe functions the G120 GSD file must be installed
in the control system e.g. SIMATIC S7.
Input and output address, 6 byte each (input and otuput address are identical)
• Byte 0 (process data 0), Bit 0:
• Byte 0 (process data 0), Bit 1:
• Byte 1 (process data 1), Bit 0:
Table 6-8
1
2
9
Table 6-9
1
2
9
Control Units CU240S
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
Intput addresses for PROFIsafe signals
Address
Function
E 0.0
STO bit from inverter
E 0.1
SS1 bit from inverter
...
E 1.0
SLS bit from inverter
Output addresses for PROFIsafe signals
Address
Function
A 0.0
STO bit to inverter
A 0.1
SS1 bit to inverter
...
A 1.0
SLS to from inverter
STO
0 = selected
SS1
0 = selected
SLS
0 = selected
Communication
6.2 Cyclic Communication
1 not selected
1 not selected
1 not selected
131